EcoSystem
®
Energi Savr Node
TM
Installation Guide
Lutron
®
|
9
EcoSystem
®
Energi Savr Node
TM
|
Installation Guide
Simple application: Out of Box Functionality (requires no programming)
Preconfigured mode (QSN-2ECO-S only)
Two zones with occupancy sensors
* Six fixtures shown on each link. However, up to 64 ballasts,
drivers, or
EcoSystem
devices can be connected per link.
Out of Box Functionality
This section describes the default functionality that the unit will
present when first installed.
Inputs (Occupancy, Daylight, and IR):
Occupancy sensor/
IR Receiver
Daylight sensor
QSN-2ECO-S
Connected to
input group 1
Controls link 1 only Controls link 1 only
Connected to
input group 2
Controls link 2 only Controls link 2 only
Connected to
input group 3
Controls both links
Controls both links
Connected to
input group 4
Controls both links
Controls both links
QSN-1ECO-S
Connected to
input groups 1,
3, or 4
Controls link 1 only Controls link 1 only
Occupancy Sensors (Occ)
• Corresponding
zones will turn on when the occupancy sensor is
in the occupied state (closed) and off when in the unoccupied
state (open).
Daylight Sensors (Photo)
• Corresponding
zone light levels will increase when light sensed
by daylight sensor decreases.
• Corresponding
zone light levels will decrease when light sensed
by daylight sensor increases.
IR Receivers (IR)
• Corresponding
zones respond to On, Off, Scene, Raise, and
Lower commands from compatible IR transmitters (see IR Re-
ceiver literature for compatible transmitters and
EcoSystem
wallstations).
Contact Closure Input (CCI)
• Activates a scene using a normally-open (NO) momentary clo
-
sure from a dry contact closure device. Default scene sends all
fixtures to 100%.
Emergency Contact Closure Input (Emerg)
• Emergency contact closure input is normally closed (NC). The
EcoSystem Energi Savr Node
unit is shipped with a jumper pre-
installed.
• If the Emergency input is open, the
EcoSystem Energi Savr
Node
unit will remain in Emergency Mode, which will force bal-
lasts and drivers to their emergency level (100% by default) and
disable control from inputs and QS devices.
• When the Emergency input is closed or jumpered,
EcoSystem
Energi Savr Node
unit zones will return to the settings or levels
they were at prior to entering Emergency Mode.
QS Wallstations
• All seeTouch
®
QS wallstations are Scene keypads by default.
• Scenes 1-16 will turn all the lights on to the preset levels shown
in the table below:
Scene #
Light Level: All Zones
1, 5-16
100%
2
75%
3
50%
4
25%
• Scene Off will turn all the lights Off.
Zone 1
Zone 2
W
indow
W
indow
Occupancy
Sensor
Perimeter
Interior
Occupancy
Sensor
EcoSystem
Energi Savr
Node
unit
Wired
to input
group
1
Wired
to input
group
2