background image

EcoSystem

®

 Energi Savr Node

TM

 Installation Guide

Lutron

®

  

|

  9

EcoSystem

®

 Energi Savr Node

TM

 

|

 Installation Guide

Simple application: Out of Box Functionality (requires no programming)

Preconfigured mode (QSN-2ECO-S only)

Two zones with occupancy sensors
*  Six fixtures shown on each link. However, up to 64 ballasts, 

drivers, or 

EcoSystem

 devices can be connected per link.

Out of Box Functionality

This section describes the default functionality that the unit will 
present when first installed.

Inputs (Occupancy, Daylight, and IR):

Occupancy sensor/
IR Receiver

Daylight sensor

QSN-2ECO-S

Connected to 
input group 1

Controls link 1 only Controls link 1 only

Connected to 
input group 2

Controls link 2 only Controls link 2 only

Connected to 
input group 3

Controls both links

Controls both links

Connected to 
input group 4

Controls both links

Controls both links

QSN-1ECO-S

Connected to 
input groups 1, 
3, or 4

Controls link 1 only Controls link 1 only

Occupancy Sensors (Occ)

• Corresponding 

zones will turn on when the occupancy sensor is 

in the occupied state (closed) and off when in the unoccupied 
state (open).

Daylight Sensors (Photo)

• Corresponding 

zone light levels will increase when light sensed 

by daylight sensor decreases.

• Corresponding 

zone light levels will decrease when light sensed 

by daylight sensor increases.

IR Receivers (IR)

• Corresponding 

zones respond to On, Off, Scene, Raise, and 

Lower commands from compatible IR transmitters (see IR Re-
ceiver literature for compatible transmitters and 

EcoSystem 

wallstations).

Contact Closure Input (CCI)

 • Activates a scene using a normally-open (NO) momentary clo

-

sure from a dry contact closure device. Default scene sends all 
fixtures to 100%.

Emergency Contact Closure Input (Emerg)

• Emergency contact closure input is normally closed (NC). The 

EcoSystem Energi Savr Node

 

unit is shipped with a jumper pre-

installed.

• If the Emergency input is open, the 

EcoSystem Energi Savr 

Node

 

unit will remain in Emergency Mode, which will force bal-

lasts and drivers to their emergency level (100% by default) and 
disable control from inputs and QS devices.

 • When the Emergency input is closed or jumpered, 

EcoSystem 

Energi Savr Node

 

unit zones will return to the settings or levels 

they were at prior to entering Emergency Mode.

QS Wallstations

• All seeTouch

®

 QS wallstations are Scene keypads by default.

• Scenes 1-16 will turn all the lights on to the preset levels shown 

in the table below:

Scene #

Light Level: All Zones

1, 5-16

100%

2

75%

3

50%

4

25%

• Scene Off will turn all the lights Off.

Zone 1

Zone 2

W

indow

W

indow

Occupancy 

Sensor

Perimeter

Interior

Occupancy 

Sensor

EcoSystem 
Energi Savr 

Node 

unit

Wired 

to input 

group 

1

Wired 

to input 

group 

2

Summary of Contents for EcoSystem Energi Savr Node

Page 1: ...power wiring 3 EcoSystem Link wiring 4 Input group wiring 5 Contact closure inputs 6 QS link wiring 7 Applications 9 Out of box functionality 9 System Programming Connection 10 Troubleshooting 11 Warr...

Page 2: ...es The EcoSystem Energi Savr Node unit counts as 1 QS device and 1 100 zones on the QS link depending on system programming In a system a maximum of 100 wired or wireless daylight sensors 100 wired or...

Page 3: ...the following instructions to wire line voltage to the EcoSys tem Energi Savr Node unit WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all pow...

Page 4: ...must be accessed by a certified electrician following local codes 1 Turn power off 2 Remove metal outer panel cover 3 Remove internal plastic line voltage shield 4 Wire the EcoSystem link from the Eco...

Page 5: ...it are used for troubleshooting If wiring is exposed when accessing buttons and LEDs the unit must be accessed by a certified electrician following local codes Note The EcoSystem Energi Savr Node unit...

Page 6: ...ergency level 100 by default and disable control from inputs and QS devices When the closure is restored ballasts and or drivers will return to their previous level Note The EcoSystem Energi Savr Node...

Page 7: ...ode unit counts as 1 QS device and 1 100 zones See diagram on the right for QS link wiring 1 Connect terminals 1 3 and 4 to all EcoSystem Energi Savr Node units 2 Each EcoSystem Energi Savr Node unit...

Page 8: ...coSystem Energi Savr Node unit Sivoia QS Shade Sivoia QS Smart Power Panel seeTouch QS Wallstations QS Control Link Sivoia QS Smart Power Panel Sivoia QS Shade seeTouch QS Wallstations EcoSystem Energ...

Page 9: ...one light levels will decrease when light sensed by daylight sensor increases IR Receivers IR Corresponding zones respond to On Off Scene Raise and Lower commands from compatible IR transmitters see I...

Page 10: ...ts connected to an EcoSystem Energi Savr Node unit via the QS Link except when part of a Quantum system Energi Savr Node app is required to program EcoSystem Energi Savr Node units except when part of...

Page 11: ...ash per 7 seconds More than one supply powering link QS QS Link Green 1 flash per second Green 1 flash per 7 seconds Link disconnected communication lost Green 5 flashes per second Incorrect data Off...

Page 12: ...LURE TO MEET ANY DUTY INCLUDING OF GOOD FAITH OR OF REASONABLE CARE NEGLIGENCE OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON S WRITTEN CONSENT ARISI...

Reviews: