Using LEDs to troubleshoot

WARNING! Danger of Shock. May result in serious 
injury or death.

 DO NOT WIRE WHEN LIVE! Switch off 

power to all power feeds via circuit breaker or isolator 
before wiring or servicing the 

EcoSystem Energi Savr 

Node 

unit.

Buttons and LEDs in the unit are used for troubleshooting. 
If wiring is exposed when accessing buttons and LEDs, the 
unit must be accessed by a certified electrician, following 
local codes.

LED Behavior

LED

Normal 
operation

Problem  
indicator

Probable cause

PWR (Power) Green:  

Continuous On

Green: 5 flashes 

per second

General system failure

ECO1 

ECO2  
(

EcoSystem

 

Status)

Green: 1 flash 

per second

Red:  

Continuous on

Link externally shorted

Red/Green:  

alternating 1 flash 

per second

Link slowed because of 

over-temperature

Red: 1 flash per 

second

Link stopped because of 

over-temperature

Red: 5 flashes per 

second

Miswire or 

EcoSystem

 

link error

Red: 1 flash per 7 

seconds

More than one supply 

powering link

QS (QS Link)

Green: 1 flash 

per second

Green: 1 flash per 

7 seconds

Link disconnected,  

communication lost

Green: 5 flashes 

per second

Incorrect data

Off 

No connection ever 

made

Ethernet

Green:  

Flashing

Off

Ethernet not connected

Yellow:  

Continuous On Off

Ethernet not connected

Test

Off

Red: 5 flashes per 

second

Test failed

Temp

Off

Red: 5 flashes per 

second

Over-temperature

Red: continuous 

On

Over-temperature, unit 

disabled

Input LED Behavior

LED

LED Behavior

Description

OCC 

(Occupancy 

Sensor)

Continuous On

Sensor detects Vacancy

1 flash per second

Sensor detects Occupancy

Off

Sensor never detected

PHOTO 

(Daylight  

Sensor )

Continuous On

Sensor is detected

Flashing

Sensor information  

transmitting on the QS link

Off

Sensor never detected/sensor 

not seeing light

IR 

(Infrared  

Receiver)

Continuous On

Receiver is detected

Flashing

IR button press detected

Off

Receiver never detected

CCI 

(Contact  

Closure Input)

Continuous On

Contact detected/open

Flashing

Contact closed

Off

Contact never detected

Emerg 

(Emergency 

Contact Closure 

Input)

Continuous On

Normal operation/Contact 

Closed/Jumpered

Rapid flash

Emergency Mode/Contact 

Open/Jumper missing

Summary of Contents for EcoSystem Energi Savr Node

Page 1: ...power wiring 3 EcoSystem Link wiring 4 Input group wiring 5 Contact closure inputs 6 QS link wiring 7 Applications 9 Out of box functionality 9 System Programming Connection 10 Troubleshooting 11 Warr...

Page 2: ...es The EcoSystem Energi Savr Node unit counts as 1 QS device and 1 100 zones on the QS link depending on system programming In a system a maximum of 100 wired or wireless daylight sensors 100 wired or...

Page 3: ...the following instructions to wire line voltage to the EcoSys tem Energi Savr Node unit WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all pow...

Page 4: ...must be accessed by a certified electrician following local codes 1 Turn power off 2 Remove metal outer panel cover 3 Remove internal plastic line voltage shield 4 Wire the EcoSystem link from the Eco...

Page 5: ...it are used for troubleshooting If wiring is exposed when accessing buttons and LEDs the unit must be accessed by a certified electrician following local codes Note The EcoSystem Energi Savr Node unit...

Page 6: ...ergency level 100 by default and disable control from inputs and QS devices When the closure is restored ballasts and or drivers will return to their previous level Note The EcoSystem Energi Savr Node...

Page 7: ...ode unit counts as 1 QS device and 1 100 zones See diagram on the right for QS link wiring 1 Connect terminals 1 3 and 4 to all EcoSystem Energi Savr Node units 2 Each EcoSystem Energi Savr Node unit...

Page 8: ...coSystem Energi Savr Node unit Sivoia QS Shade Sivoia QS Smart Power Panel seeTouch QS Wallstations QS Control Link Sivoia QS Smart Power Panel Sivoia QS Shade seeTouch QS Wallstations EcoSystem Energ...

Page 9: ...one light levels will decrease when light sensed by daylight sensor increases IR Receivers IR Corresponding zones respond to On Off Scene Raise and Lower commands from compatible IR transmitters see I...

Page 10: ...ts connected to an EcoSystem Energi Savr Node unit via the QS Link except when part of a Quantum system Energi Savr Node app is required to program EcoSystem Energi Savr Node units except when part of...

Page 11: ...ash per 7 seconds More than one supply powering link QS QS Link Green 1 flash per second Green 1 flash per 7 seconds Link disconnected communication lost Green 5 flashes per second Incorrect data Off...

Page 12: ...LURE TO MEET ANY DUTY INCLUDING OF GOOD FAITH OR OF REASONABLE CARE NEGLIGENCE OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON S WRITTEN CONSENT ARISI...

Reviews: