 Installation Guide

Lutron

®

  

|

  3

EcoSystem

®

 Energi Savr Node

TM

 

|

 Installation Guide

QS LINK

ECO1

ECO1

RESET

ECO2

TEST

GROUP 1

+20V

OCC 

1

PHO

TO

 1

IR 

1

CO

M

+24V

MU

X

PWR

TEMP

TEST

MU

X

CO

M

GROUP 2

+20V

OCC 

2

PHO

TO

 2

IR 

2

CO

M

GROUP 3

+20V

OCC 

3

PHO

TO

 3

IR 

3

CO

M

GROUP 4

+20V

OCC 

4

PHO

TO

 4

IR 

4

CO

M

CONTACT CLOSURE

ETHERNET

CC

I

CO

M

EMER

G

CO

M

ECO1

H

N

G

Step-by-step installation instructions
Step 1: Mounting the 

EcoSystem Energi Savr 

Node 

Unit

Note: Mount the 

EcoSystem

 

Energi Savr Node

 

unit

 

in a posi-

tion where it can be easily located and accessed if service or 
troubleshooting is necessary.

• For indoor use only! 
• NEMA, Type 1 enclosure, IP20.
• Remove metal outer panel cover. 
• Remove internal plastic line voltage shield.
• Choose panel mounting location so line voltage wiring is at least 

6 ft (1.8 m) from audio or electronic equipment and associated 
wiring (prevents radio frequency interference).

• Install in accordance with all national and local electrical codes.

Mechanical Dimensions

All dimensions shown as inches (mm)

Control Power Wiring

11.25 

(285.75)

10.25 

(260.35)

0.20  

(5.16) dia.

1.00 

(25.40)

1.5 

(38.10)

1.22 

(30.99)

1.66 

(42.16)

1.31 

(33.27)

0.88 

(22.35)

1.22 

(30.99)

1.62 

(41.15)

9.25 

(234.95)

7.50 

(190.50)

3.16 

(80.26)

13.25 

(336.55)

Step 2: Control power wiring

The 

EcoSystem

 

Energi Savr Node 

unit

 

operates at 120-277 V . 

Use the following instructions to wire line voltage to the 

EcoSys-

tem

 

Energi Savr Node 

unit.

WARNING! Danger of Shock. May result in serious 
injury or death.

 DO NOT WIRE WHEN LIVE! Switch off 

power to all power feeds via circuit breaker or isolator 
before wiring or servicing the 

EcoSystem

 

Energi Savr 

Node 

unit.

Buttons and LEDs in the unit are used for troubleshooting. 

If wiring is exposed when accessing buttons and LEDs, the 

unit must be accessed by a certified electrician, following 

local codes.  

1. Turn power off.
2. Remove metal outer panel cover.
3. Remove internal plastic line voltage shield.
4. Use 14 AWG to 12 AWG (2.5 mm

2

 to 4.0 mm

2

) conductors (de-

pending on breaker rating) to feed the control power wiring. The 
device draws less than 0.5 A.

5. Wire the line voltage cables to the terminals labeled H (Hot), N 

(Neutral) and G (Ground).

6. Reinstall internal plastic line voltage shield.
7. Turn on the circuit breaker or isolator to power up the 

EcoSys-

tem

 

Energi Savr Node 

unit. The Power LED on the 

EcoSystem

 

Energi Savr Node 

unit will illuminate continuously when prop-

erly energized. If the LED does not light, turn off power, then 
check the control power wiring.

8. Turn power off.

Control Power Wiring:

• Two (2) 14 AWG to 12 AWG 

(2.5 mm

2

 to 4.0 mm

2

)

• Strip length: 3/8 in (8.5 mm)
• Torque: 7 in-lbs (0.79 N

m)

Hot (H)

Neutral (N)

Ground (G)

Do not use

QS LINK

ECO1

ECO1

RESET

ECO2

TEST

GROUP 1

+20V

OCC 

1

PHO

TO

 1

IR 

1

CO

M

+24V

MU

X

PWR

TEMP

TEST

MU

X

CO

M

GROUP 2

+20V

OCC 

2

PHO

TO

 2

IR 

2

CO

M

GROUP 3

+20V

OCC 

3

PHO

TO

 3

IR 

3

CO

M

GROUP 4

+20V

OCC 

4

PHO

TO

 4

IR 

4

CO

M

CONTACT CLOSURE

ETHERNET

CC

I

CO

M

EMER

G

CO

M

ECO1

H

N

G

Line Voltage Shield

Summary of Contents for EcoSystem Energi Savr Node

Page 1: ...power wiring 3 EcoSystem Link wiring 4 Input group wiring 5 Contact closure inputs 6 QS link wiring 7 Applications 9 Out of box functionality 9 System Programming Connection 10 Troubleshooting 11 Warr...

Page 2: ...es The EcoSystem Energi Savr Node unit counts as 1 QS device and 1 100 zones on the QS link depending on system programming In a system a maximum of 100 wired or wireless daylight sensors 100 wired or...

Page 3: ...the following instructions to wire line voltage to the EcoSys tem Energi Savr Node unit WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all pow...

Page 4: ...must be accessed by a certified electrician following local codes 1 Turn power off 2 Remove metal outer panel cover 3 Remove internal plastic line voltage shield 4 Wire the EcoSystem link from the Eco...

Page 5: ...it are used for troubleshooting If wiring is exposed when accessing buttons and LEDs the unit must be accessed by a certified electrician following local codes Note The EcoSystem Energi Savr Node unit...

Page 6: ...ergency level 100 by default and disable control from inputs and QS devices When the closure is restored ballasts and or drivers will return to their previous level Note The EcoSystem Energi Savr Node...

Page 7: ...ode unit counts as 1 QS device and 1 100 zones See diagram on the right for QS link wiring 1 Connect terminals 1 3 and 4 to all EcoSystem Energi Savr Node units 2 Each EcoSystem Energi Savr Node unit...

Page 8: ...coSystem Energi Savr Node unit Sivoia QS Shade Sivoia QS Smart Power Panel seeTouch QS Wallstations QS Control Link Sivoia QS Smart Power Panel Sivoia QS Shade seeTouch QS Wallstations EcoSystem Energ...

Page 9: ...one light levels will decrease when light sensed by daylight sensor increases IR Receivers IR Corresponding zones respond to On Off Scene Raise and Lower commands from compatible IR transmitters see I...

Page 10: ...ts connected to an EcoSystem Energi Savr Node unit via the QS Link except when part of a Quantum system Energi Savr Node app is required to program EcoSystem Energi Savr Node units except when part of...

Page 11: ...ash per 7 seconds More than one supply powering link QS QS Link Green 1 flash per second Green 1 flash per 7 seconds Link disconnected communication lost Green 5 flashes per second Incorrect data Off...

Page 12: ...LURE TO MEET ANY DUTY INCLUDING OF GOOD FAITH OR OF REASONABLE CARE NEGLIGENCE OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON S WRITTEN CONSENT ARISI...