Activate Loads in Bypass
®
e
t
a
l
p
b
u
S
g
n
i
h
c
t
i
w
S
d
n
a
g
n
i
m
m
i
D
30
7
2
P
G
C
r
o
f
e
d
i
u
G
n
o
i
t
a
ll
a
t
s
n
I
16
A. Complete load wiring.
B. Check that the bypass jumpers are in place.
These jumpers protect from load faults and must be used to check load wiring when it is installed or modified.
WARNING!
Shock hazard. May result in serious
injury or death if panel is not wired correctly.
Verify the panel is fed from the correct voltage.
C. Turn circuit breaker feeding the Module Interface ON.
Check that the power indicator LED on the Module Interface is ON. If the power indicator LED is OFF, verify that
the 24 V
~
terminals from the transformer are connected to the board, the power plug for the Module Interface
is plugged in and wired to the enclosure terminal blocks, and that the circuit breaker is turned ON.
D. Turn circuit breaker feeding module 1 ON.
Load(s) associated with the circuit should energize, the breaker should not trip, and the total load current must
be within the circuit breaker's limit and less than or equal to 16 A.
Turn next circuit breaker ON.
E.
LOAD TERMINALS
AC RMS current
Bypass jumper
Load circuit
wiring
Power indicator LED
at the top of HWI-MI-120
A feed mis-wire or loss of a feed neutral can cause over-voltage damage to the equipment.
NOTICE:
The next corresponding load(s) should energize, the breaker should not trip, and the total load current must be
within the circuit breaker's limit and less than or equal to 16 A.
Repeat step E for each circuit with
completed load wiring.
F.