Temporary Lighting

®

®

Installation Guide for CGP2730 Dimming and Switching Subplate  15

 

Do not install a temporary distribution panel. For 
temporary lighting needs, each input breaker can 
supply power to a load with the pre-installed bypass 
jumper present. The bypass jumper also protects 
the module from load faults.

Bypass jumper protects the 
module from load faults by 
tying the input feed to the 
load, bypassing the module.

WARNING

!

 Shock hazard. May result in 

serious injury or death if panel is not wired 
correctly. Verify the panel is fed from the 
correct voltage. 

NOTE: 

Do NOT remove bypass jumpers at 

this point, they protect the modules from 
load faults.

Bypass jumpers 
shown in white

Bypass jumpers come 
pre-installed in the module 
terminal blocks for your 
convenience and will allow for 
temporary lighting until your 
system is programmed.

Module Terminal 
Blocks

LOAD TERMINALS

LOAD TERMINALS

                A feed mis-wire or loss of a feed 
neutral can cause over-voltage damage to 
the equipment.

NOTICE:

Summary of Contents for CGP2730

Page 1: ...s ce lieu 4A CAUTION PRECAUCI N ATTENTION 4U Do not place HW RPM 4U 120 or HW RPM 4A 120 modules in this location No coloque HW RPM 4U 120 o HW RPM 4A 120 m dulos en esta ubicaci n Ne placez pas HW RP...

Page 2: ...gh 8 4U 4A 4A Four Output Dimming 4A cannot be placed in locations 1 through 4 Output Load Ratings Module Type Rating 4R 64 A total per module 4 circuits module 16 A per circuit 4U 16 A total per modu...

Page 3: ...UL compliance of the enclosure Existing Labels Remove all existing labels except for the UL Label Panel can be flush mounted or surface mounted and still be compatible with Lutron s front cover The Lu...

Page 4: ...120 HW RPM 4J 120 HW RPM 4FSQ 120 SH3 H4 SH5 N R1 L1 R2 L2 R3 N Quiet Fan Speed Control Module 120 V 50 60 Hz HW RPM 4M 120 L3 R4 L4 H H Installation Label Place the included label in the panel as sho...

Page 5: ...g a 29 size drill bit Clean inside of enclosure and reinstall subplate and secure with provided screws STEP ONE Place subplate into left side of the enclosure STEP TWO Slide subplate right the four gr...

Page 6: ...mm 2 mm or 2 3 8 in 10 mm 10 mm 10 mm 3 8 in 3 8 in 20 in lb 20 in lb 3 2 N m 2 8 N m 4 N m 25 in lb 35 in lb 6 4 AWG 0 AWG 1 4 1 8 AWG or 2 14 10 AWG 2 5 4 2 mm 6 1 0 1 2 mm 6 2 5 4 2 mm 2 mm or 2 3...

Page 7: ...2 14 10 AWG 2 5 4 2 mm 6 1 0 1 2 mm 6 2 5 4 2 mm 2 mm or 2 3 8 in 10 mm 10 mm 10 mm 3 8 in 3 8 in 20 in lb 20 in lb 3 2 N m 2 8 N m 4 N m 25 in lb 35 in lb 18 10 AWG 0 75 6 0 mm2 8 mm 5 16 in 0 6 0 8...

Page 8: ...g Module 4J 4 Output Fan Speed Control Module 4FSQ Use the following information to wire the newly installed modules Terminal Blocks N DH H DH DH DH Terminal blocks for 4U 4J and 4FSQ modules come pre...

Page 9: ...les and should be installed in place of the default terminal blocks as needed 4 RED WIRES BLACK WIRES WHITE WIRE N SH H SH H SH H SH H 4 3 3 2 2 1 1 4 4 3 2 3 2 2 3 4 4 3 2 1 Notice Make sure that no...

Page 10: ...ed in place of the default terminal blocks as needed N L H R L R L R L R Notice Make sure that no wires are pinched when installing the modules Pull check all wires to ensure a good connection and tha...

Page 11: ...ch load circuit Feed Wiring Mains Voltage Wiring Preferred feed wiring entry for subplate is between Load terminal blocks and Neutral Busses Run wiring so that line mains voltage wiring will be at lea...

Page 12: ...d Hot DH and or Switched Hot SH terminal blocks are grouped by a module 4 output circuits each in numbered order in the top right of the subplate The numbers represent the sequential circuit in the pa...

Page 13: ...load wiring to the appropriate load terminal set for each circuit and Neutral to the Neutral bus corresponding to the terminal block numbers in the vertical terminal blocks located in the center of t...

Page 14: ...on Termination at the processor end of the chain is included on HomeWorksR 8 Series processor boards so an LT 1A is not required On HomeWorksR QS processors link termination is also required at the pr...

Page 15: ...load bypassing the module WARNING Shock hazard May result in serious injury or death if panel is not wired correctly Verify the panel is fed from the correct voltage NOTE Do NOT remove bypass jumpers...

Page 16: ...are connected to the board the power plug for the Module Interface is plugged in and wired to the enclosure terminal blocks and that the circuit breaker is turned ON D Turn circuit breaker feeding mod...

Page 17: ...p y b e h t e r o t s d n a e v o m e R possible future use C Turn circuit breakers ON Notice Bypass jumper Module with 4 outputs shown Remove Bypass Jumpers Make sure installation is complete and po...

Page 18: ...nnecter plusieurs interrupteurs pour d charger l quipement avant l entretien WARNING AVERTISSEMENT Riesgo choque el ctrico Puede resultar enlesiones graves o la muerte Puede necesitarse m s de un conm...

Page 19: ...Notes Installation Guide for CGP2730 Dimming and Switching Subplate 19...

Page 20: ...lutron com http forums lutron com Warranty For Warranty information please see the Warranty enclosed with the product or visit www lutron com TechnicalDocumentLibrary HomeWorks_Warranty pdf www lutro...

Reviews: