21
Rated operating conditions:
- supply voltage 20…24…40 V a.c./d.c. or
85…230…253 V a.c./d.c.
- supply voltage frequency
40…50/60…440 Hz
- ambient temperature
0…23…55ºC
- relative air humidity
< 95% (inadmissible condensation of
water vapor)
- external magnetic field
< 400 A/m
- working position
any
Storage and transport conditions:
- ambient temperature
-20…70 ºC
- relative air humidity
< 95% (inadmissible condensation of
water vapor)
Ensured protection levels:
- from frontal housing side
IP 40
- from terminal side
IP 20
Overall dimensions:
45 x 120 x 100 mm
Weight :
0.25 kg
SMC casing: for mounting on a 35 mm DIN rail
Electromagnetic compatibility:
- noise immunity
acc. to EN 61000-6-2
- noise emissions
acc. to EN 61000-6-4
Safety requirements acc. to EN 61010-1:
- installation category
III
- pollution level
2
Maximal phase-to-earth working voltage:
- for supply circuits
300 V
- for other circuits
50 V