20
Data Field:
In the correct response, the slave device can return data on the data field (some information requested by
the master unit).
In the erroneous response, the slave device returns the terror code on the data field. It defines the slave
device conditions, which causes the error.
An example of master device request and erroneous slave device response is presented below. Data are in
the hexadecimal shape.
Example: request
slave
address
function
variable
address
Hi
variable
address
Lo
number of
variables
Hi
number of
variables
Lo
checksum
0A
01
04
A1
00
01
4F
LRC
Example: erroneous error
slave
address
function
error
code
checksum
0A
81
01
73
LRC
In this example, the master device addresses the request to the slave unit numbered 10 (oHa).
The function with the code (01) is not implemented in the concentrator, then the device returns the erroneous
response with the error code nr 01. It indicates the forbidden function in the slave device. Possible error
codes and their meanings are presented in the table below.
code
meaning
01
forbidden function
02
forbidden data address
03
forbidden data value
04
request being in realization
05
impossible request realization
8. TECHNICAL DATA
Serial port I:
- baud rate 1200, 2400, 4800, 9600, 19200,
38400, 57600, 115200 bit/s
- mode
ASCII: 8N1, 7E1, 7O1,7N2
RTU: 8N2, 8 E1, 8O1, 8N1
- interface 2 x RS-485
Serial port II:
- baud rate 1200, 2400, 4800, 9600, 19200,
38400, 57600, 115200 bit/s
- mode
ASCII: 8N1, 7E1, 7O1,7N2
RTU: 8N2, 8 E1, 8O1, 8N1
- interface RS-485, RS-232
USB 1.1 – wire no longer than 3 m
Transmission protocol: MODBUS – ASCII, RTU
Power consumption
≤
4 VA