Lucent Technologies Lineage
®
2000 Battery Management System ED-83241-30
3 - 20 Installation
Issue 5 March 1997
4. Slide the Hall-effect current sensor (CS) onto the 2 AWG
wire coming off the negative battery post of cell 23 or 24,
depending on the configuration, to the terminal plate
before re-torquing the nut on the terminal. Be sure the
arrow marked on the Hall-effect sensor is pointing away
from the negative battery post (Figure 3-16).
5. After re-torquing the battery post nuts to 60 in-lb, insert the
two temperature sensors between battery cells 15-16 and
9-10. Thermal grease may be used to ease insertion.
6. Attach both the temperature sensors and Hall-effect sensor
to their appropriate connectors on the volt/temp sensor
cable set and the current sensor cable set, respectively.
7. Repeat for second battery string.
DIP Switch
Configuration
1. Refer to Section 4 for help in determining proper DIP
switch settings for your particular application.
2. Use DIP switch SW100-1,2 to select T1. Use DIP switch
SW100-3,4 to select T2/MJT.
Note
These cable sets contain current limiting resistors in series
with all voltage monitoring points.
Note
If accuracy at very low currents is desired, refer to Section 5
before installing the Hall-effect current sensor.
Table 3-B: SW100 Settings
T1 Setpoint
T2/MJT Setpoint
°C/°F
1
2
°C/°F
3
4
20/68
25/77
30/86
35/95
1
1
0
0
1
0
1
0
40/104
45/113
50/122
55/131
1
1
0
0
1
0
1
0