Lucent Technologies Lineage
®
2000 Battery Management System ED-83241-30
Issue 5 March 1997
Product Description 2 - 1
2
Product Description
Battery
Management
System (CP5)
Specifications
Table 2-A: Battery Management System (CP5) Specifications
Operating Voltage Range
-40.0 to -60.0 Vdc
Input Power
12 watts maximum;
In-line 1-1/3A alarmed fuse
Operating Temperature Range 0° - 50°C (32° - 122°F)
Altitude
200 to 13,000 ft. (-61 to 3962 m);
For altitudes of 5000 to 13,000 ft. (1524 to
3962 m), reduce the maximum ambient
temperature 3.6°F (2°C) for every 1000 ft.
Humidity
10 - 95% noncondensing
Electrostatic Discharge
IEC 801-2 Levels 2 & 4 (14 kV & 15 kV) at
40% relative humidity
Radiated Emission
FCC Level A
Electromagnetic Immunity
10 V/m over a range of 20 to 1000 MHz
Alarm Contacts
Four sets of Form C contacts, one for each
system alarm: 500 mA, 60 VDC max
Battery Sensor Set
Accommodates sensor sets for up to two strings
on base unit
Temperature Sensor
Two per battery string, with one additional
sensor per battery plant to monitor ambient
temperature