5. Function Code Table
5-9
Note)
1) When PAR_07 is set to “User Define”, PAR_08 will be displayed.
2) If PAR_24 (Auto-tuning type selection) is set to No.1 “Standstill”, the order of display in
PAR_25 (Auto-tuning range setting) will be None
ALL1
Rs Tuning
Lsigma
If/Tr/Ls
Tune.
3) Caution: PAR_33 (Enc Scale) Code is necessary only in the case of installation of SIN/COS
Encoder option board, Don’t modify the default value “X1” when not using SIN/COS Encoder
board If you modify the value, the normal operation isn’t possible. For any extra information in
detail, refer to the option dedicated manual.
4) It will be displayed when PAR_35(Selection for motor inertia tuning) sets as ‘Yes’.
5.4. Function group (FUN_[][])
CODE
NO.
Comm.
Addr
CODE NAME
LCD DISPLAY
SETTING DATA
Adjustment
During Run
RANGE
UNIT
DEFAULT
FUN_00
-
Jump for quick view
Jump code
1 ~ 85
-
-
Yes
FUN_01 7401
RUN/STOP command
source selection
Run/Stop Src
0 (Terminal 1)
1 (Terminal 2)
2 (Keypad)
3 (Option)
-
0
(Terminal
1)
No
FUN_02 7402
Speed setting source
selection
Spd Ref Sel
0 (Analog)
1 (Keypad1)
2 (Keypad2)
3 (Option)
6 (Line SPD Ref)
1)
7 (Line SPD Opt)
1)
-
1
(Keypad1)
No
FUN_03 7403
Stop mode selection
Stop mode
0 (Decel)
1 (Free-run)
-
0 (Decel)
No
FUN_04 7404
Max. motor speed
Max Speed
400.0 ~ 3600.0
rpm
1800.0
No
FUN_05 7405
Min. motor speed
Min Speed
2)
0.0 ~ 500.0
100.0
No
FUN_12 740C
M
ul
ti-
st
ep
s
pe
e
d
0
Speed 0
0.0 ~ Max Speed
0.0
Yes
FUN_13 740D
1
Speed 1
0.0
Yes
FUN_14 740E
2
Speed 2
0.0
Yes
FUN_15 740F
3
Speed 3
0.0
Yes
FUN_16 7410
4
Speed 4
0.0
Yes
FUN_17 7411
5
Speed 5
0.0
Yes
FUN_18 7412
6
Speed 6
0.0
Yes
FUN_19 7413
7
Speed 7
0.0
Yes
FUN_20 7414
JOG speed
Jog Speed
100.0
Yes
FUN_21 7415
Dwell Speed
Dwell Speed
100.0
No