4. Trial Operation
4-13
4.8.3 Adjusting Ai1 Gain and Bias (example of analog input Ai1 setting)
①
①
①
①
Out Y2(Gain) Adjustment of Analog input
Apply 10V or 20mA between AI1 ~ 5G
(for setting by potentiometer, adjust it to Max).
Adjust the other multi analog input terminals in same manner.
Key
Handling
Loader Display
Description
Initial LCD display
PROG
Pressing [PROG] key, shows in upper
side the percent of input to output and in
low side the gain value be set presently.
▲
If you try to adjust the gain to show
100.00%, Press [
▲
(Up)] key repeatedly
and set to be 102.00%.
ENT
After adjusting Gain, if you enter [ENT]
key, the adjusted gain value is saved.
②
②
②
②
Out Y1(Bias) Adjustment of Analog input
Apply 0V or 0mA between AI1 ~ 5G
(for setting by potentiometer, adjust it to Min).
Adjust the other multi analog input terminals in same manner.
Key
Handling
Loader Display
Description
Initial LCD display
PROG
Pressing [PROG] key, shows in upper
side the percent of input to output and in
low side the Bias value be set presently.
▲
If you try to adjust the Bias to show
0.00%, Press [
▲
(Up)] key repeatedly
and set to be 0.00%.
ENT
After adjusting Bias, if you enter [ENT]
key, the adjusted Bias value is saved.
AIO
▶
Ai1 Out Y2
06 100.00 %
AIO
▶
Ai1
98.00 %
06 Gain 100.00 %
AIO
▶
Ai1 100.00 %
06 Gain
102.00 %
AIO
▶
Ai1 Out Y2
06 102.00 %
AIO
▶
Ai1 Out Y1
04 0.00 %
AIO
▶
Ai1 0.18 %
04 Bias
0.00 %
AIO
▶
Ai1 0.00 %
04 Bias
0.18 %
AIO
▶
Ai1 Out Y1
04 0.18 %