3. Installation and Wiring
3-29
SV2800 ~ 5000iV5(Press) (for AC/DC products)
3.5.2 Function description of auxiliary terminal block
Symbol
Terminal Name
Terminal Description
Input Power
AC1, C2
Auxiliary power
input
Inputs single-phase
AC input source
220V (-10 ~ +10%),
50/60Hz
3.5.3 Wiring and Precaution of auxiliary terminal block
①
Connect the auxiliary power supply through insulated transformer separated
with main power supply.
②
User polyvinyl chloride insulated wire for auxiliary power cable.
③
Use the cable above 0.5mm
2
(20 AWG).
Terminal of the Auxiliary
Power Supply