AC Reactor Specifications
You can install an AC reactor to prevent the capacitors and generators from overheating or
being damaged when the power source voltage is unbalanced.
When you install an AC reactor, connect the AC reactor cables to the R, S, and T terminals on
the inverter. Installation of an AC reactor is not necessary if a DC reactor is already installed in
the inverter.
To avoid power loss resulting from the incorrect installation of an AC reactor, contact LSIS
Customer Support to ensure that your model type and application requires the installation of
an AC reactor.
Refer to the following specifications tables to choose an appropriate AC reactor for your
application.
Inverter capacity
AC reactor specifications
Heavy duty
Normal duty
mH
A
mH
A
0008iS7-2
2.13
5.7
1.20
10
0015iS7-2
1.20
10
0.88
14
0022iS7-2
0.88
14
0.56
20
0037iS7-2
0.56
20
0.39
30
0055iS7-2
0.39
30
0.28
40
0075iS7-2
0.28
40
0.20
59
0110iS7-2
0.20
59
0.15
75
0150iS7-2
0.15
75
0.12
96
0185iS7-2
0.12
96
0.10
112
0220iS7-2
0.10
112
0.07
160
0300iS7-2
0.07
160
0.05
200
0370iS7-2
0.05
200
0.044
240
0450iS7-2
0.044
240
0.038
280
0550iS7-2
0.038
280
0.026
360
0750iS7-2
0.026
360
0.02
500
0008iS7-4
8.63
2.8
4.81
4.8
Summary of Contents for SV-iS7 series
Page 1: ......
Page 5: ......
Page 126: ...Basic Functions 115 Basic Functions Code Description V1 Quantizing ...
Page 223: ...212 Peripheral Devices Group 2 ...
Page 224: ...Peripheral Devices Peripheral Devices 213 Group 3 ...
Page 225: ...214 Peripheral Devices Group 4 ...
Page 231: ...220 Peripheral Devices TYPE 1 Maximum 400 Watts TYPE 2 Maximum 600 Watts ...
Page 255: ......