Basic Functions
116
6.1.3.2
Setting a Frequency Reference for -10
–
+10 V Input
Set DRV-07
(Frequency reference source) to “2 (V1)”, and then set IN
-
06 (V1 Polarity) to “1
(bipolar)”. Use the output voltage from an external source to provide an input to V1.
[External source application]
[Internal source (VR) application]
[V1 terminal wiring]
[Bipolar input voltage and output frequency]
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
DRV
07
Frequency reference
source
Freq Ref Src
2
V1
0
–
9
-
IN
01
Frequency at
maximum analog
input
Freq at 100%
60.00
0
–
max.
frequency
Hz