RCI-1502 HRT Tele Boom Manual
3.4.
Display Functions
The RCI-1502 has 2 LCD display windows and 6 front panel push buttons. The
display panel can also be grouped into four parts as follows:
3.4.1. “Approach to Rated Capacity” Indication Lamps
This is the uppermost part of the di splay which contains three coloured
lamps to indicate “ap proach to rated capacity ”. Factory settings are as
follows:
•
Green: 50 to 84%, Amber: 85 to 99%, Red: 100 to 110%
•
Amber lamp flashes when first trip point is rea ched (i.e. 8 5%
Rated Capacity) plus an intermittent audible alarm.
•
Red lamp will flash at 100% of rated capacity plus a continuous
audible alarm.
•
Red lamp will stop flashing and will stay ON when the lifted load
exceeds 110% of SWL plus a c ontinuous audible alarm. Crane
motion controls are also activated at this stage if fitted.
3.4.2. Numerical LCD for Various Functions
This is a numerica l LCD display , just below the
indication lamps
mentioned abov e, which shows th
e LENGTH, ANGLE, RADIUS,
S.W.L., FALLS, and DUTY status.
This window is also used to display ERROR codes when any errors are
detected. The error function cannot be manually selected but will be
displayed automatically if there are any errors. Please refer to Section
6. “Troubleshooting” for the meaning and description of the error codes.
The above functions are selected by pressing the SELECT button on
the front panel. The selected function is indicated by the lamp next to
the labels. The display functions are as follows:
LENGTH
The numerical display shows the BOOM length, in unit selected (feet or
metres), for the winch selected.
ANGLE
The numerical display shows the
current working angle in degrees
which is read from the main boom angle sensor.
RADIUS
The numerical display shows the current working radius, in unit selected
(feet or metres), for the winch selected.
SWL
The numerical display shows the current maximum safe working load in
unit selected (kilopounds or tonnes). The S.W.L. will depend on the
current crane configuration (duty ), winch selected (if twin winch), the
maximum linepull and the falls selected.
Summary of Contents for RCI-1502 HRT
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 14: ......
Page 22: ......
Page 44: ......
Page 52: ......
Page 56: ......
Page 58: ......
Page 59: ...Appendix 8 1 Data Logging on RCI Systems ...
Page 60: ......
Page 66: ...Data Logging on RCI Systems Example Lift Cycles ...
Page 71: ...Appendix 8 2 Drawings ...
Page 72: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 77: ...APPROVED BY TOL 0 0 0 1 2 3 4 55 26 2 0 7 2 8 9 1 1 1 1 0 7 5 6 2 ...
Page 79: ...APPROVED BY TOL 0 0 0 1 22 3 4 5 6 0 22 2 1 7 8 98 1 7 8 98 7 8 98 7 8 98 1 0 9 8 3 6 8 3 ...
Page 80: ... APPROVED BY 0 1 2 22 3 3 3 TOL 4 4 23 4 232 22 3 242 4 2 32 2 3516 7 8 7 7 9 2 3 42 4 2 ...
Page 81: ... APPROVED BY 0 1 2 22 3 3 3 TOL 4 4 23 4 232 22 5 0 42 4 2 3617 8 9 8 8 2 ...
Page 82: ......
Page 83: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......