Function Setup
This menu is access protected.
The alarm sound period, the number of times the alarm message is to be sent (if more than once), and,
if required, a delay on activation of the alarm are set in this menu.
It is also possible to monitor the current battery voltage (if the battery is connected).
It is important to “Save” configuration if changes have been made.
Setting
Function
Function
indicates if the voltage free contact set is set to Normally Closed or Normally
Open.
Alarm Delay
Delay from registration of alarm till activation of alarm.
Control Delay
Delay from activation of the
control
button on the front panel till activation of the
alarm function.
Email Repeat
Set up time frame for repeating alarm text message per alarm incidence.
Max Email Repeat
Set up the number of times alarm text message is to be sent per alarm incidence.
Sound Period
The period from one beep starts till next beep starts. Can be set to 1/10 of 1-
255sec. E.g. sound periode is set to 10 it takes 1sec from beep starts till next beep
incl. period of silence.
Sound Duty Cycle
Lenght of beep in percent of sound periode. E.g. sound peride is set to 10 and
sound duty cycle to 50 - the lenght of the beep will equal the lenght of silence. If
you want longer or shorter beeps the sound duty cycle can be set to a higher or
lower percentage.
Battery Alarm
Alarm at low battery voltage can be activated in this field.
Battery Voltage
Display the measured battery voltage (the value is only measured when the unit is
in operation). In case Battery Alarm is set to “on” the alarm is activated when the
battery voltage falls below 7.5V.