M07 - COMMUNICATION (DMG110 only) UdM Default Range
P07.01
Serial node address 01 01-255
P07.02
Serial speed bps 9600 1200
2400
4800
9600
19200
38400
57600
115200
P07.03
Data format 8 bit – n 8 bit, no parity
8 bit, odd
8bit, even
7 bit, odd
7 bit, even
P07.04
Stop bits 1 1-2
P07.05
Protocol Modbus RTU Modbus RTU
Modbus ASCII
P07.n.01
– Serial address (node) for the communication protocol.
P07.n.02
– Communication port bitrate.
P07.n.03
– Data format. 7-bit settings available for ASCII protocol only.
P07.n.04
– Number of stop bits.
P07.n.05
– Communication protocol selection.
M08 - LIMIT THRESHOLDS (LIMn, n=1..4) UdM Default Range
P08.n.01
Reference measure OFF OFF- (measures)
P08.n.02
Function Max Max – Min –
Min+Max
P08.n.03
Upper threshold 0 -9999 - +9999
P08.n.04
Multiplier x1 /100 – x10k
P08.n.05
Delay s 0 0.0 – 1000.0
P08.n.06
Lower threshold 0 -9999 - +9999
P08.n.07
Multiplier x1 /100 – x10k
P08.n.08
Delay s 0 0.0 – 1000.0
P08.n.09
Normal status OFF OFF-ON
P08.n.10
Latch OFF OFF-ON
Note: this menu is divided into 4 sections, for limit thresholds LIM1..4
P08.n.01
– Defines which multimeter measurement the limit threshold is applied to.
P08.n.02
– Defines the function of the limit threshold. It can be:
Max
= LIMn active when measurement exceeds P08.n.03. P08.n.06 is the reset threshold.
Min
= LIMn active when measurement is below P08.n.06. P08.n.03 is the reset threshold.
Min+Max
= LIMn active when measurement is above P08.n.03 or below P08.n.06.
P08.n.03 and P08.n.04
– Define the upper threshold, which results from multiplying value P08.n.03 by P08.n.04.
P08.n.05
– Trip delay on upper threshold.
P08.n.06, P08.n.07, P08.n.08
– as above, with reference to the lower threshold.
P08.n.09
– Permits inversion of the status of limit threshold LIMn.
P08.n.10
– Defines whether the threshold is stored and must be reset manually (ON) or is reset automatically (OFF).
M09 - ALARMS (ALAn, n=1..4) Default Range
P09.n.01
Alarm source OFF OFF-LIMx
P09.n.02
Channel number (x) 1 1-4
P09.n.03
Latch OFF OFF-ON
P09.n.04
Priority Low Low - High
P09.n.05
Text ALAn (text: 16 characters
Note: this menu is divided into 4 sections, for alarms ALA1..4
P09.n.01
– Signal that causes the alarm. It can be when a threshold (LIMx) is exceeded.
P09.n.02
– Channel number (x), with reference to the previous parameter.
P09.n.03
– Defines whether the alarm is stored and must be reset manually (ON) or is reset automatically (OFF).
P09.n.04
– If the alarm has a priority of high, its activation switches the display to the alarm page automatically and it is displayed with the alarm icon. If instead it is set to low priority, the page does not change and
it is displayed with the ‘information’ icon.
P09.n.05
– Free text for alarm. 16 characters max.