MAIN MENU
– To access the main menu, press the
and
buttons together when the motor is stopped.
– This provides you access to the following functions:
– Like the inputs/outputs, there are internal variables (bit) which may be associated to the outputs or combined each other. For example, limit thresholds can be associated to the measurements performed by the
soft starter (voltage, current etc.). In this case, the internal variable, named LIMx, will be activated when the measurement is beyond the limits defined by the user by means of the respective setting menu.
– The following table shows all the internal variables managed by the ADXL with their range (number of variables for each type).
– Select the required function by pressing
and
.
– Press START to confirm.
PASSWORD-PROTECTED ACCESS
– The password is used to enable or block access to the setup menu and the command menu.
– The password is deactivated and access is free on new equipment (default). If the passwords are enabled, they must be entered to access the equipment (the passwords are numeric).
– See P03 Password menu for how to enable and define passwords.
– There are two password access levels, according to the entered code:
– User level access – allows you to display parameters but not to modify them.
– Advanced level access - the same rights as the user level, with the addition of being able to edit all settings.
– If the password is enabled, you are prompted to enter the password when you call up the main menu.
– The password setting window will appear:
– Use the
and
buttons to change the value of the current digit in the range 0 to 9.
– Press START to move to the next digit on the right.
– The respective unlock message will appear when the entered password corresponds to the User level password or to the Advanced level password.
– After having unlocked the password, access will remain enabled until:
• the soft starter is switched off.
• the soft starter is reset (after closing the settings menu).
• two minutes elapse without the operator touching any button.
• press the STOP button to abort setting the password.
EVENT LIST
– The ADXL can store a list of the last 60 events, which is stored even in absence of power supply.
– The events stored are the following:
• Power supply on/off
• Start/stop of the motor
• Overcoming of current/torque limit thresholds
• Alarms (both events of starting alarm and ending alarm)
• Access to the parameters setup
• Use of commands
• Serial communication
• Memory transfer from CX02 dongle
– To access to the event list you have to enter in the main menu (by pressing in contemporary the buttons
and
), with button
select the voice 02 EVENTS and press START.
– It will be displayed the most recent event, with the event code Exxx and a description of the event.
– With the buttons
and
you can scroll the events. With the button
PREV you can see the previous events and with the button
NEXT the next events up to the most recent one.
– The display notify when you reach the oldest event or the most recent event.
– While you are watching an event, if you press START you can see from how many hours, minutes and seconds the event is happened from the power up of the soft starter. This is useful to give an idea of the time
interval between an event and the next one.
– To exit from the event list press STOP or the buttons
and
in contemporary.
INPUTS, OUTPUTS, INTERNAL VARIABLES
– The ADXL's inputs and outputs are identified by a code and a sequential number. For example, the digital inputs are named INPx, where x is the input number. In the same way, the digital outputs are denominated
OUTx and the communications ports COMx.
– The respective configuration menus allow you to map any function to any input/output. The default programming maps the most commonly used functions, to facilitate commissioning the soft starter.
FUNCTION CODE DISPLAY
Set password (if enabled – see menu P03 Password ) PAS PASSWORD
Launch SETUP menu SET SETUP
Enter EVENTS log list EVE EVENTS
Launch COMMANDS menu CnD COMMANDS
Starter serial number Sn SERIAL N.
Starter firmware revision Sr REV. NUM.
Quit main menu ESC EXIT
CODE DESCRIPTION RANGE
INPx Digital inputs 1…3
OUTx Digital outputs 1…3
COMx Communication ports 1
CODE DESCRIPTION RANGE
LIMx Limit thresholds on measurements 1…4
REMx Variables controlled remotely 1…8
UAx User alarms 1…4