LOVATO ELECTRIC DMK40 Software Manual Download Page 19

 

 

  Code: MSGB202$0500.doc                                       18/06/2004                                                                       P.  19 / 20

 

 
 
 
 

APPENDIX A – Connection modes 

 
Connection via standard modem 

To make a remote connection via a switched telephone line the use of a pair of modems is necessary.  
Lovato Electric guarantees correct operation of the connection using modems of the following type: 
 

• 

3-Com U.S. Robotics 56K model 5630 

 
Though correct operation is possible also with modems of other types, in this manual all the configuration 
commands (variables depending on the manufacturer) and the connection diagrams will refer to the above-
mentioned modem model. 
 

Though very simple in conception, connection via modem requires that the installer have a minimum 
of experience concerning the problems connected with serial communication, modem programming, 
types of telephone lines, etc. In an attempt to simplify the configuration procedure as far as possible, 
we have subdivided the operations to be carried out in the following steps: 
 
1.  Modem configuration at the DMK end 

From the DMK end the modem must be configured before it can be used. Configuration serves to 
implement the following functions: 

• 

Disable the echo   

• 

Set a communication speed (this must be the default speed for DMK also) 

• 

Permanently store the two previous settings as default at switch on 
 
To make these configurations, the modem to be connected to the RS232/RS485 converter will have to 
be momentarily connected to the PC with its standard cable. Then start the PM.EXE program (supplied 
together with this software) and press the 

Program modem 

button

Wait for the confirmation message 

and then disconnect the modem from the PC and connect it to the DMK. The PM.EXE program transmits 
the following configuration string to the modem: 
 

AT E0 &N6 &U6 &W0 

<CR>

  

 

(commands valid for modem model 5630) 

 
To select higher baud rates in the modem, digit Nx & Ux, whereas x is the rate code to be obtained. 
Take into account the rate to select is the one at the multimeter end. 
If the program PM is used, the AT&Nx and AT&Ux string must be changed in the modem.txt file found in 
the same directory where the PM program is installed. 
 
If the user is familiar with terminal emulation programs (such as Windows Hyperterminal) this 
programming can be done manually without the aid of the PM.EXE program. In this case, it will be 
necessary to set the serial interface at 9600 Baud, 8 bit, No parity, 1 stop bit and type in the above string 
from the keyboard. On pressing return the modem will answer with OK confirming that programming has 
taken place. 

 

2. DMK 

configuration 

Also the DMK needs a configuration to be able to converse with the modem.  

• 

From the front panel of each DMK, enter the serial communication setup menu (see the DMK Addendum 
Manual)  

• 

Check the serial address (parameter P.41). If several DMKs are connected to a RS-485 bus, set each of 
them with a progressive serial address starting from 001. 

• 

On each unit, select the Modbus ASCII protocol (parameter P.44 set to ASC). 

• 

If you want the DMK to answer when modem rings (modem without auto-answer) then set parameter 
P.45 to 001, only for the DMK with serial address 01.  

• 

Otherwise, if you want the modem to answer automatically itself, then enable the modem auto-answer, 
setting its parameter S0 to 001 (with command ATS0=1 &W0) and leave the first DMK with P45 to 000. 

 
 
 

Summary of Contents for DMK40

Page 1: ...n diagram direct 3 Basic principles 5 Main window 5 System configuration 6 Important note 9 Display menu 10 Data collection 10 Graphs 11 Front panel 14 Password 14 Communication menu 15 Online 15 Offl...

Page 2: ...and be familiar with Windows operating system commands The software is delivered on a CD with two different installation procedures The standard installation procedure used with the first releases of...

Page 3: ...onverter as indicated in the Connection diagrams paragraph below Comply scrupulously with the polarity of the Rs485 cables 4 We recommend use of a Rs232 Rs485 converter furnished by Lovato If you inte...

Page 4: ...Serial port settings window while for the DMK it is selected with parameter P 42 see Addendum The connection polarity of the DMKs and of the converter to the RS 485 bus must be correct all the A term...

Page 5: ...vidual measurement can be displayed and printed Main window The main window of the program contains all the menus and the toolbars for access to the various functions As they may modify the configurat...

Page 6: ...ystem configuration is a very important phase as regards definition of software functioning In particular if several multimeters are connected attention must be paid to programming the parameters of e...

Page 7: ...op If the selected measure indicates all three phases it is sufficient the measure value of one of the three phases is greater than threshold 1 to trigger the datalogger The same procedure is done to...

Page 8: ...ntly saved record is lost Transmits the settings made Note on transmitting the settings all the data saved in the DMK40 will be lost Receives the settings saved in the DMK40 View the DMK real time clo...

Page 9: ...figure 2 2 When using modem connection all this setting can be used only if the remote connection is done always to the same DMK network that is if there is only one record in the Modem index because...

Page 10: ...th the Display Data collection menu or clicking on the matching icon on the toolbar Fig 3 1 Display Data collection Sampling date and time Number of records selected Values of the variables sampled Di...

Page 11: ...aph menu or click on the matching icon of the toolbar This type of graph is very similar to t hat of an oscilloscope The time is indicated on the X horizontal axis The horizontal time scale is common...

Page 12: ...Code MSGB202 0500 doc 18 06 2004 P 12 20...

Page 13: ...Code MSGB202 0500 doc 18 06 2004 P 13 20...

Page 14: ...d or holding down of the keys Note The quality of the graphic representation of the front panel may vary according to the graphic resolution of your PC and or the monitor settings used Fig 7 1 Display...

Page 15: ...dow The system passes automatically in Offline mode when the user opens the Configuration window Modem Call To connect to one or several DMK via a couple of modems it is necessary to select the Modem...

Page 16: ...shaking messages with the answering modem At the end of this procedure if everything has been carried out correctly the PC status bar will show a message informing the user that connection has taken p...

Page 17: ...the DMK The following four menus are available Basic setup basic settings such as CT VT ratio etc Advanced setup settings of the digital outputs Capacitor overload setup parameters relating to the ca...

Page 18: ...eful when programming a set of multimeters with the same settings or when you want to file the original settings of a system To save the parameters on disk select the Parameters Save to file menu and...

Page 19: ...r the confirmation message and then disconnect the modem from the PC and connect it to the DMK The PM EXE program transmits the following configuration string to the modem AT E0 N6 U6 W0 CR commands v...

Page 20: ...below Click on Dial At this point the modem at the PC end calls the DMK modem After a few rings the DMK modem and the program switch automatically to the online mode To end the connection choose Modem...

Reviews: