M14 – PROGRAMMABLE INPUTS (INPn, n=1…8) UoM Default Range
P14.n.01 INPn input function OFF (see Input functions
table)
P14.n.02 Channel number x OFF OFF / 1…99
P14.n.03 Type of contact NO NO/NC
P14.n.04 Delay ON s 0.05 0.00-600.00
P14.n.05 Delay OFF s 0.05 0.00-600.00
Note: This menu is divided into 8 sections that refer to 8 possible digital inputs
P14.n.01
– Choice of the function for the selected input (see programmable input functions table).
P14.n.02
– Channel number associated with the function programmed in the previous parameter. If the input function is set to Setpoint selection cos
x, and this input must select cos
3, the value must be set to 3.
P14.n.03
– Select the type of contact:
NO
(Normally Open) or
NC
(Normally Closed).
P14.n.04
– Contact closing delay for selected input.
P14.n.05
– Contact opening delay for selected input.
M15 – PASSWORD UoM Default Range
P15.01 Enable password OFF OFF-ON
P15.02 User level password 1000 0-9999
P15.03 Advanced level password 2000 0-9999
P15.04 Remote access password OFF OFF/1-9999
P15.01
– If set to OFF, password management is disabled and anyone has access to the settings and commands menu.
P15.02
– With P15.01 enabled, this is the code number to access user level. See Password access chapter.
P15.03
– As per P15.02 but referred to Advanced level access.
P15.04
– If set to a numeric value, this becomes the code to specify via serial communication before sending commands from a remote control site.
INPUT FUNCTIONS TABLE
– The following table shows all the functions that can be attributed to the INPn programmable digital inputs.
– Each input can be set for an reverse function (NO - NC), delayed energising or de-energising at independently set times.
– Some functions require another numeric parameter, defined in the channel number x specified by parameter
P14.n.02
.
– Refer to menu M14 Programmable inputs for more details.
FUNCTION
DESCRIPTION
OFF
Disabled input
Configurable
Free user configurable input INPx. Used for instance to generate a user alarm UA or to count on a CNT counter
Automatic mode
When active, switches system to AUT mode
Manual mode
When active, switches system to MAN mode
Select cosphi setpoint x
When active, selects the cosphi setpoint x (x=1…3)
Keyboard lock
Locks front keyboard
Settings lock
Locks access to setup menu and commands menu
Alarm inhibition
Selectively disables alarms having inhibit property set to ON.
Command menu Cxx
When active, runs the command Cxx (see COMMAND MENU)
OUTPUT FUNCTION TABLE
– The following table shows all the functions that can be attributed to the OUTn programmable digital outputs.
– Each output can be configured so it has a normal or reverse (NOR or REV) function.
– Some functions require another numeric parameter, defined in the channel number x specified by parameter
P04.n.02
.
– Refer to menu M04 MASTER OUTPUTS for more details.
FUNCTION
DESCRIPTION
OFF
Output always de-energised
ON
Output always energised
Step x
Capacitor step no.x
Global alarm 1
Energised when global alarm 1 is active
Global alarm 2
Energised when global alarm 2 is active
Global alarm 3
Energised when global alarm 3 is active
Fan
Panel ventilation fan
Manual mode
Active when the controller is in MAN mode
Automatic mode
Active when the controller is in AUT mode
Limit threshold LIMx
Output driven by LIM limits (x= 1…16)
Pulse PULx
Output driven by PUL pulses ( x = 1…6)
Remote variable REMx
Output is remotely controlled by REM variable
Alarms A01-Axx
When the selected Axx alarm is present, the output is activated (xx= 01… alarm number)
Alarms UA1..UAx
When the selected UAx user alarm is present, the output is activated (x=1… 8)