STARTING THE GENERATOR:
a.
At the first start leave the panel in ON for one minute, the fuel pump is filling the fuel circuit, it does not need
any bleeding.
b. Press the "START" button: the display shows a decreasing number (preheating glow plugs). Reached zero, is
used in an automatic way the starter.
b. If there are no problems, the engine starts and the display shows the value of the output voltage (within 30
seconds if the generator set does not supply voltage the panel turns the engine off).
DASHBOARD MAY PREVENT STARTING IF:
a. Oil pressure warning light is not connected or pressure sensor in open circuit (caution when engine fails to
start, repeat the operation only after the warning light has returned to light)
b.Water temperature thermistor not connected or
DASHBOARD STOP THE ENGINE IF:
a. Oil warning light switched on while the engine running.
b. Water high temperature alarm with thermal contact on the engine.
c.Impeller break alarm with thermal contact on the exhaust elbow (riser).
d. Water high temperature alarm with thermistor on the engine set to 115°C.
e. Current overload alarm for a time of 120 seconds.
f. Lack of voltage in one or more phases.
Turn the key on the picture pressing ON : the writing OFF appears on the display.
Summary of Contents for LMG 14000 MONOFASE
Page 1: ...MANUALE USO E MANUTENZIONE USE AND MAINTENANCE MANUAL LMG 9000 LMG 14000 LMG 18000 ...
Page 2: ......
Page 21: ...INSTALLAZIONE INSTALLATION 19 ...
Page 35: ...SPECIFICHE TECNICHE TECHNICAL SPECIFICATIONS SCHEMA DI COLLEGAMENTO WIRING DIAGRAM 33 ...
Page 40: ...USO USE 38 ...
Page 42: ...IDENTIFICAZIONE IDENTIFICATION 18 17 16 15 13 12 14 11 10 9 40 ...
Page 45: ...CONTROLLI CHECK 43 ...
Page 63: ...MANUTENZIONE MAINTENENCE 61 ...
Page 77: ......
Page 78: ......