Moving the tank
Logano G334X – 6 720 811 237 (2014/05)
8
3
Moving the tank
This section details how to move the boiler safely.
Moving the boiler with boiler cart
▶ Position transport equipment (e. g. pallet truck/forklift) at the back
of the boiler.
▶ Secure packaged boiler to the hand truck.
▶ Move the packaged boiler to the installation location.
▶ Remove the straps and the cardboard packaging.
▶ Loosen the retaining screws.
▶ Lift the boiler at the sides and slide to the edge of the pallet.
▶ Place a pipe under the boiler and roll it on additional pipes to the
installation location.
▶ Place the boiler in its final position.
Fig. 4
Moving the tank
4
Placing the boiler
This section explains how to set up and position the boiler correctly at
the installation location.
4.1
Installation location requirements
4.2
Clearances
Position the boiler with the recommended wall clearances. Reducing
these to the minimum clearances makes the boiler more difficult to
access.
The base or foundation on which the boiler is to stand must be perfectly
flat and level. The boiler may stand on a base made of combustible
material, but not on carpet.
A space of at least 33 inches (840 mm) is required in front of the boiler
with the door open to allow sufficient accessibility for operation and
maintenance. When the door is closed, a minimum clearance of 2 inches
(50 mm) is required at the front and sides, a wall clearance of 6 inches
NOTICE:
Risk of system damage from impact shocks!
Fragile components could be damaged.
▶ Observe the transport instructions on the packaging.
NOTICE:
System damage due to improper transport!
▶ Protect sheet metal parts, flue gas pipe, burner, and
control unit during transport.
▶ Do not use these components to lift the boiler.
Dispose of the packaging material in an environmentally
prudent fashion.
WARNING:
Risk of injury if load is inadequately secured
during transportation!
▶ Use suitable transport equipment
(e. g. pallet truck/forklift).
▶ When transporting, secure the boiler to prevent it
from falling.
6 720 810 547-04.1T
DANGER:
Danger posed by explosive and combustible
materials!
▶ Never use or store easily flammable materials (paper,
curtains, clothing, thinners, paints etc.) near the
boiler.
▶ Maintain a clearance of 16 inches (415 mm) from the
boiler.
NOTICE:
Risk of system damage due to freezing!
▶ Install the heating system that it will not be exposed
to freezing conditions.
NOTICE:
Damage to the building due to insufficient load
capacity of the floor!
▶ Before setting the boiler up, check the load capacity
of the floor.
NOTICE:
Boiler damage due to contaminated
combustion air.
▶ Do not use cleaning agents that contain chlorine or
halogenated hydrocarbons (e.g. in spray cans,
solvents and cleaning agents, paints, glues).
▶ Avoid excessive dust accumulation (building dust).
Wall clearance
Dimension
[inch]
[mm]
A
33
840
B
6
155
C
2
50
Table 7 Wall clearances
Where applicable, allow extra wall clearances for
additional components such as a DHW tank, pipe joints,
vent pipe silencer or other components on the flue gas
side, etc.