INSTALLATION
VENTING REQUIREMENTS
Minimum vertical runs shall be no less than 2.4 metres.
Changes of direction from the vertical should be avoided where possible.
NOTE:
Vertical run to be at maximum possible distance before any
change in direction.
Where change of direction is unavoidable refer to NZS 5261-1996 Standard / AG601
1995 Australian gas association standard.
Where gradient of lateral (horizontal) runs are required LOGAIRE recommends a
minimum angle of 45% with a minimum run of 600 mm height of vertical flue before
gradient, provided a 1.5 meter vertical run is fitted after any off-set,
Refer to diagram 7.
DIAGRAM 7
Any deviation from minimum and maximum recommended dimensions may effect
performance of the fire.