750 Control Panel Operation and Troubleshooting
8
463-3000-08 revised Sept 16, 2013
When the configured stop conditions exist, the panel reduces the engine speed per the throttle profile and stops the
engine. If the configured start conditions exist before the shutdown process is complete the engine will return to the
previous speed until the stop condition exists.
Automatic Start/Stop Warning! When the key is turned to the autostart position and
a start condition exists, the panel will start
immediately
!
Always
configure parameters
by turning the key to run.
Do not
configure the panel in the autostart position!
Always
use lock out/tag
out procedures when servicing autostart equipment!
Start and Stop Events
The Start and Stop Events are determined by the combination of Start/Stop Mode and Function. See the table below
for
Start/Stop Modes
Sngl Switch
Switch one controls automatic
operation.
Dual Switch
Both switch inputs control
automatic operation.
Transducer
The transducer input controls
automatic operation.
Xducer & Sw
The transducer input controls
automatic operation with dual
switch mode as the backup. The
switch inputs override the
transducer if actuated when the
transducer is not calling for an
automatic cycle.
Start/Stop Functions
Empty
Uses the selected mode to
reduce
the level or pressure.
Fill
Uses the selected mode to
increase
the level or pressure.
Maintain Out
Uses the transducer to maintain the level or pressure at or
below
the target.
Maintain In
Uses the transducer to maintain the level or pressure at or
above
the target.
Mode
▼
Function
►
Empty
Fill
Maintain Out
Maintain In
Sngl Switch
Start
SW1 Close
SW1 Open
SW1 Close
SW1 Open
Stop
SW1 Open
SW1 Close
SW1 Open
SW1 Close
Dual Switch
Start
SW1 and SW2 Close
SW1 and SW2 Open
SW1 and SW2 Close
SW1 and SW2 Open
Stop
SW1 and SW2 Open
SW1 and SW2 Close
SW1 and SW2 Open
SW1 and SW2 Close
Transducer
Start
Above High Set Point
Below Low Set Point
Above High Set Point
Below Low Set Point
Stop
Below Low Set Point
Above High Set Point
Below Low Set Point
Above High Set Point
Xducer & Sw
Start
Above High Set Point
or
SW1 and SW2 Close
Below Low Set Point
or
SW1 and SW2 Open
Above High Set Point
or
SW1 and SW2 Close
Below Low Set Point
or
SW1 and SW2 Open
Stop
Below Low Set Point
or
SW1 and SW2 Open
Above High Set Point
or
SW1 and SW2 Close
Above High Set Point
or
SW1 and SW2 Close
Below Low Set Point
or
SW1 and SW2 Open
Note:
When the switch inputs are the source of the start event in Xducer & Sw mode, only the switches will stop the
engine.
R
P
M
Time
Idle
Intermediate
Run
Start
Event
Warm Up
seconds
Ramp Up
seconds
Intermediate
seconds
Ramp to Run
seconds
At Run Speed
Stop
Event
Ramp Down
seconds
Cool Down
minutes
Engine
Stop
Engine
Running