750 Control Panel Operation and Troubleshooting
22
463-3000-08 revised Sept 16, 2013
Start on Sec
Selects the maximum number of seconds the starter
can be engaged
Settings Menu
This submenu allows the user to configure CANplus hardware.
Governor
Selects between
Elect
(electronically governed) and
Mech
(mechanically governed) engines modes. For mechanically
governed engines the
CANplus I/O Board
functions as an ECU, broadcasting engine parameters such as oil pressure
and temperature on the CANbus.
Note
Switching governor modes requires cycling power before calibrating the RPM. The
CANplus Configurator
must be
used to configure mechanical engine parameters.
CP750 CAN Add
Selects the address used by the display to communicate with the CANplus I/O board. The default I/O Board address is
128.
Note
Engine data is always transmitted using address 0 in mechanically governed mode.
Warning
Incorrectly configuring the CP750 CAN Address prevents the display from receiving I/O Board data for the display
menus and can result in data collisions on the CANbus.
Calibrate RPM
Calibrates the tachometer input for mechanically governed engines to allow the CANplus I/O board to measure the
engine speed. This signal may be provided by an alternator frequency tap, proximity switch. An optional
amplifier/divider can be added for use with a magnetic pickup.