All units are equipped with manual reset blocked vent and flame
roll-out / flame interlock switches. These temperature switches
are located in the controls compartment and in the relief
opening of the boiler’s built-in draft hood. Each switch has a
red reset button. In the event the system has actuated to shut off
the main burner gas supply, wait for the boiler to cool, then
press the red reset to return the boiler to operation. Op er a tion
of a blocked vent and/or flame roll-out / interlock switch usually
indicates a problem with the venting system, obstruction of the
heat ex chang er flue gas passageway and/or a combustion air
supply prob lem. The cause for operation of the blocked vent
and/or flame roll-out / interlock switch must be determined and
corrected. If the boiler cannot be restored to normal operation,
contact a qualified ser vice in stall er, service agency or the gas
supplier.