Installation & Service Manual
1
Determine boiler location
NOTICE
Clearances from combustible construction
are noted on the appliance rating plate.
Location of unit
1. Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations
cannot be avoided, it is recommended that a suitable drain
pan, adequately drained, be installed under the appliance.
The pan must not restrict combustion air flow. Under no
circumstances is the manufacturer to be held responsible
for water damage in connection with this appliance, or any
of its components.
2. The appliance must be installed indoors where it is
protected from exposure to wind, rain and weather.
3. The appliance must be installed so that the ignition system
components are protected from water (dripping, spraying,
rain, etc.,) during appliance operation and service
(circulator replacement, control replacement, etc.,).
4. Appliances located in a residential garage and in adjacent
spaces that open to the garage and are not part of the
living space of a dwelling unit must be installed so that all
burners and burner ignition devices have a minimum
clearance of not less than 18" (46cm) above the floor. The
appliance must be located or protected so that it is not
subject to physical damage by a moving vehicle.
5.
DO NOT
install this appliance in any location where
gasoline or flammable vapors are likely to be present.
6. All units have been approved for alcove installation (an
ALCOVE is a closet enclosure without a front door).
7. The appliance must not be installed on carpet.
8. All units have been approved for use on combustible
surfaces.
9. Allow sufficient space for servicing pipe connections,
pump and other auxiliary equipment, as well as the
appliance.
Figure 1-1_
Alcove Installation - Models 45,000 -
180,000 Btu/hr
18 "
FRONT
18 "
LEFT
6 " RIGHT
14"
TOP
6 " REAR
Recommended Service Clearances:
Left - 24”
Front - 24”
18 "
FRONT
18 "
LEFT
6 " RIGHT
29"
TOP
6 " REAR
Recommended Service Clearances:
Left - 24”
Front - 24”
Figure 1-2_
Alcove Installation - Models 215,000 -
260,000 Btu/hr
9