23
To install the flue connection to the HCB86CE boiler the following procedure should be followed:
1.
Check you have all items shown in Section 10.3.2.
2.
Check the flue temperature sensor (supplied with the boiler) is securely located into the hole on the exhaust
transition.
If the flue temperature sensor is not fitted, the flue gas may exceed the maximum temperature
rating of the flue and can lead to severe personal injury, death or substantial property damage.
3.
Insert the air intake transition (Item 5) into the intake connection reducer and tighten the worm drive clip.
4.
To the bottom (exhaust) connection of the concentric adaptor fit one of the 80mm 90 elbow, then fit the 80mm
x500mm flue pipe cut to length as in Section 10.3.2.
5.
To the side (intake) connection of the concentric adaptor, fit the remaining 90
elbows.
6.
Fit the Concentric adapter (item 3) to the exhaust flue pipe and air inlet elbows
7.
Fit the flue gas test point (Item 2) and clamp using its locking band.
The completed transition kit should look like the photos shown below.
REAR VIEW TRANSITION KIT HCB86CE
SIDE VIEW TRANSITION KIT HCB86CE
10.3.3
TRANSITION
KIT
FITTED
TO