14
8.3
CLEARANCES
The location chosen for the equipment must permit the provision for a satisfactory flue system and, where necessary,
an adequate air supply. The location must also provide adequate space for servicing and air circulation around each
unit. This includes any electrical trunking laid across the floor and to the appliance.
See
PLANT-ROOM INSTALLATION CLEARANCES (mm)
For dimensions/clearances. Further details regarding locations are given in BS5440 or BS6644 as appropriate.
8.4
CONDENSATE DRAIN
The condensate drain is located on the left hand side of the boiler. It is fitted with a ½” PVC tee and union, this should
be connected to an appropriate condensate drain, sloping continuously away from the boiler at an angle of at least 3
(50mm per metre).
The Water Resources Act requires that trade effluent is discharged to municipal sewers between pH 6.5 and 10.0. If it
is determined that these levels cannot be achieved, an in-line condensate neutralisation kit is available from Lochinvar
Limited. This unit is capable of neutralising 4000 litres of condensate to a pH of 7.0 before releasing it to a drain.
9.0
GAS SUPPLY
The Lochinvar Herald range is suitable for use on second and third family gasses 2H - G20 - 20mbar and 3P - G31 -
37mbar. For details relating to Propane (3P) please refer to Section on LPG FUEL:
9.1
SERVICE PIPES
The local gas distributor must be consulted at the installation planning stage in order to establish the availability of an
adequate supply of gas. An existing service pipe must not be used without prior consultation with the local gas
distributor.
9.2
METERS
A new gas meter will be connected to the service pipe by the local gas distributor contractor. An existing gas meter
should be checked, preferably by the gas distributor, to ensure that it is adequate to deal with the rate of gas supply
required.
9.3
GAS SUPPLY PIPES
Supply pipes must be fitted in accordance with IGE/UP/2. Pipework from the meter to the equipment must be of
adequate size. The complete installation must be purged and tested as described in IGE/UP/1. Refer to Section on
LPG FUEL for information on LPG pipework installation guidance.
9.4
BOOSTED SUPPLIES
Where it is necessary to employ a gas pressure booster, the controls must include a low-pressure cut-off switch at the
booster inlet. The local gas distributor must be consulted before a gas pressure booster is fitted. For details of how to
connect a low-pressure cut-off switch, please refer to Section 15.0
9.5
PLANT-ROOM CONTROL VALVE
A manual valve for plant-room isolation must be fitted in the gas supply line. It must be clearly identified and readily
accessible for operation, preferably by an exit.
Summary of Contents for HERALD HCB116CE
Page 8: ...8 3 1 2 PRINCIPLE PARTS TO BE USED IN CONJUNCTION WITH TABLE 3 1 1...
Page 31: ...31 Max distance between brackets...
Page 32: ...32...
Page 33: ...33...
Page 37: ...37...
Page 53: ...53 15 8 WIRING DIAGRAM 15 8 1 WIRING DIAGRAM...
Page 54: ...54 15 9 LADDER DIAGRAM 15 9 1 LADDER DIAGRAM...
Page 92: ...92...