Display message
F
l
u
e
t
e m p
t
o o
h
i
g h
F7
p u m p
o n
9 9 9
,
5
h
r
s
Reason
Flue gas temperature limitation value exceeded 3 times within a preset time period.
Cause:
Heat exchanger polluted and not able to effectively transfer heat to the system water.
Corrective Action:
Check and clean the heat exchanger.
Cause:
Defective (partially shorted) flue gas sensor or sensor connection.
Corrective Action:
Cause:
There is no water in the unit while firing.
Corrective Action:
Cause:
Heat exchanger failure.
Corrective Action:
Display message
F
a
i
l
e d
b u
r
n
e r
s
t
a r
t
F8
p u m p
o n
9 9 9
,
5
h
r
s
Reason
Boiler not operational after 4 starting attempts.
Cause:
No spark.
Corrective Action:
Check the condition of the ignition electrode and clean/replace if necessary.
Check the distance between the electrode pin, earth pin and burner.
Check the condition of the ignition cable and replace if necessary.
Check the condition of the earth wire/connection of the ignition electrode and replace if necessary.
Check the condition of the electrode cap and replace if necessary.
Check the incoming power supply. The supply voltage must be 230 VAC 50Hz 1Ph.
Check for correct electrical earthing of the boiler.
Failed burner control system. Change the burner control PCB.
Cause:
Ignition spark, but no flame.
Corrective Action:
Ensure all isolation valves in the gas supply line are completely open. The nominal gas inlet pressure should be 20 mbar.
Check that the gas supply pipework has been correctly purged (start-up new systems).
Check if the gas valve settings are correct and adjust if necessary.
Check if the air supply to the boiler is free from obstruction.
Cause:
Flame, but not enough ionisation to establish the flame.
Corrective Action:
Check the condition of the ignition electrode and clean/replace if necessary.
Check the distance between the electrode pin, earth pin and burner.
Check the condition of the ignition cable and replace if necessary.
Check the condition of the earth wire/connection of the ignition electrode and replace if necessary.
Check for correct electrical earthing of the boiler.
Check the incoming power supply. The supply voltage must be 230 VAC 50Hz 1Ph.
Check the condition of the electrode cap and replace if necessary.
Check the condition of the ceramic insulator. Replace electrode if any sign of damage is present.
Contact Lochinvar Limited for further guidance.
Check if the gas valve opens. When there is power supply to the gas valve, but the valve does not open, the gas valve
must be replaced.
Check for moisture in the sensor connections or replace sensor.
Bleed all air from the unit so the heat from combustion can be transferred to the water and won't leave through the flue
Check the condition of the ceramic insulator. Replace electrode if any sign of damage is present.
Summary of Contents for CP-M Series
Page 5: ...5 2 0 PRINCIPAL PARTS FIGURE 2 1 REMOVABLE COMPONENTS CP M 60...
Page 6: ...6 FIGURE 2 2 REMOVABLE COMPONENTS CP M 60 CONTINUED...
Page 8: ...8 FIGURE 2 3 REMOVABLE COMPONENTS CP M 80 CP M 100...
Page 9: ...9 FIGURE 2 4 REMOVABLE COMPONENTS CP M 80 CP M 100 CONTINUED...
Page 11: ...11 FIGURE 2 5 REMOVABLE COMPONENTS CP M 120...
Page 12: ...12 FIGURE 2 6 REMOVABLE COMPONENTS CP M 120 CONTINUED...
Page 14: ...14 FIGURE 2 7 REMOVABLE COMPONENTS CP M 150 CP M 180...
Page 15: ...15 FIGURE 2 8 REMOVABLE COMPONENTS CP M 150 CP M 180 CONTINUED...
Page 94: ...94...