background image

32

The installer may be able to observe and correct certain problems 

which may arise when the unit is put into operation. HOWEVER, 

it  is  recommended  that  only  a  qualified  service  agency,  using 

appropriate test equipment, be allowed to service the heater.
As  preliminary  step,  check  wiring  against  diagram,  check  for 

grounded, broken or loose wires.  Check all wire ends to be sure 

that they are making good contact.

IGNITION CONTROL SYSTEM

Before  calling  your  qualified  service  agency,  the  following 

checklist  should  be  examined  to  eliminate  obvious  problems 

from those requiring replacement or servicing.

• 

Check that “main gas shutoff valve” is fully open and that gas 

service has not been interrupted.

• 

Check electrical supply to the water heater for possible blown 

(or tripped) fusing or power interruption. Also check the 3 amp 

fuse on the front of the digital thermostat (Fig. 2).

• 

Is  the  water  temperature  in  tank  below  the  thermostat  dial 

setting on the water heater thermostat (calling for heat)?

• 

It is possible that the high limit (E.C.O.) has functioned to shut 

off the water heater. See page 7 - High Limit Switch for reset 

procedure.  Contact  your  service  agent  if  limit  continues  to 

function to shut off water heater. 

and pour the UN•LIME into the heater.

7.  Lower container, you may have to place the container on 

its empty carton to prevent the UN•LIME from flowing back 

into the container.

8.  Let UN•LIME remain in the heater for 5 minutes and then 

lower the container to the “Drain” Position, see Figure 27.

9.  Deliming activity is indicated by foaming on the surface of the 

UN•LIME. If there is deliming activity, repeat steps 6 thru 8.

Normally, lime removal will be completed within one hour.  Severe 

build-up of lime may take longer than an hour to complete descaling.

Note:

 To check UN•LIME for continued use, place some scale 

or white chalk in a glass with a small amount of UN•LIME.  If 

the material is vigorously dissolved by the UN•LIME, it can be 

reused; if not, the UN•LIME should be replaced.

FIGURE 27.

9.  Install  the  long  plastic  male  adapter  insert  fitting  into  the 

drain valve opening of heater after applying Teflon tape or 

paste to threads. Tighten firmly by hand and use wrench or 

adjustable pliers to check for secure connection. Do not over 

tighten to avoid damage to threads and fittings.

Prepare the Up-N-Down Transfer Kit
The next step is the preparation on the Up-N-Down Transfer Kit, 

if you have not already done so:
1.  With  the  5  gallon  Up-N-Down  container  in  the  vertical 

position,  unscrew  the  plastic  vent  cap  in  the  handle  and 

pierce the plastic membrane over the vent boss under the 

cap to allow the container to vent.

Note:

  If  your  container  does  not  have  the  vent  cap  and 

vent boss, drill a 3/16” hole in the handle.  When you have 

finished deliming you will be able to plug this drilled vent with 

the stainless steel screw that is supplied with the kit.

2.  Remove the container’s cap and cut the plastic membrane 

located in the 3/4” IPT opening in the cap.  Take care to not 

damage the threads.

3.  Find the 3/4” male adapter, apply teflon tape to the threaded 

end and screw it into the 3/4” IPT opening in the cap.

4.  Put cap with male adapter back on the container and slide 

 

3/4” hose over end of male adapter and fasten in place using 

hose clamp provided.

Delime using Flo-Jug Method
5.  Slide the hose clamp over end of hose and slide hose over 

the  male  adapter  in  the  water  heater  drain  opening  and 

secure in place using hose clamp.

6.  Lift container to the “Pour” Position, see Figure 27, being 

careful to keep the vent in the handle above the liquid level 

SERVICE

SYSTEM DIAGNOSTICS

Your  water  heater  is  equipped  with  an  ignition  control  that 

incorporates a diagnostic system to assist in troubleshooting the 

water heater. The green LED codes on the ignition module are 

as follows:

TABLE 9.

2 FLASHES

5 Minutes Retry Delay

3 FLASHES

Recycle - flame failed during run

4 FLASHES

Flame sensed out of sequence

6 FLASHES

Control Internal Error

7 FLASHES

Flame rod shorted to ground

8 FLASHES

Low secondary voltage supply

If an internal control failure is indicated, replace the ignition control.
Use this diagnostic system in conjunction with “TROUBLESHOOTING” 

and the “SEQUENCE OF OPERATION” to troubleshoot the water 

heater.

ELECTRICAL SERVICING

Label  all  wires  prior  to  disconnection  when  servicing  controls. 

Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.

Summary of Contents for CLN 120080

Page 1: ...her appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor...

Page 2: ...51 TABLE OF CONTENTS SAFE INSTALLATION USE AND SERVICE 3 APPROVALS 3 GENERAL SAFETY INFORMATION 4 Precautions 5 Grounding Instructions 5 Hydrogen Gas Flammable 5 INTRODUCTION 6 Abbreviations Used 6 Q...

Page 3: ...of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances WARNING This product contains a chemical known to the St...

Page 4: ...nce with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or service technician for...

Page 5: ...ot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCE...

Page 6: ...ything on the first few pages RE AD THE ENTIRE MANUAL BE FORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER 2 The installation must conform with these instructions and the local code authority hav...

Page 7: ...of high limit switch operation the water heater cannot be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the control then ne...

Page 8: ...307 LPH 1818 1636 1309 1212 1091 935 909 818 727 654 606 595 545 519 503 467 CLN199080 199 81 80 GPH 531 478 382 354 319 273 265 239 212 191 177 174 159 152 147 137 58 307 LPH 2009 1808 1447 1340 120...

Page 9: ...he panel must be strong enough to carry the weight of the heater when full of water A service clearance of at least 24 61 cm should be maintained from serviceable parts TABLE 4 MINIMUM CLEARANCES TO C...

Page 10: ...instruction labels from the manufacturer for placement on the blanket directly over the existing labels DO inspect the insulation blanket frequently to make certain it does not sag thereby obstructing...

Page 11: ...me circulating pumps are manufactured with sealed bearings and do not require further lubrication Some circulating pumps must be periodically oiled Refer to the pump manufacturer s instructions for lu...

Page 12: ...with all gas burning equipment running at maximum rate dynamic pressure The gas supply pressure must be stable within 1 5 W C 0 37 kPa from static to dynamic pressure to provide good performance Press...

Page 13: ...1 and Water Piping Diagrams starting on page 35 TEMPERATURE PRESSURE RELIEF VALVE Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized t...

Page 14: ...ve is not intended for the constant relief of thermal expansion A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems an...

Page 15: ...ening required to provide the free area specified Where the louver and grille design and free area are not known it shall be assumed that wood louvers will have 25 free area and metal louvers and gril...

Page 16: ...hes 300 mm of the top of the enclosure shall be provided See Figure 14 The water heater shall have clearances of at least 1 inch 25 mm from the sides and back and 6 inches l50 mm from the front of the...

Page 17: ...aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 OUTDOOR AIR THROUGH TWO VERTICAL DUCTS The illustrations shown in thi...

Page 18: ...Fuel Gas Code ANSI Z223 1 and with the Category I Venting Tables If any part of the vent system is exposed to ambient temperatures below 40 F 4 4 C it must be insulated to prevent condensation Do not...

Page 19: ...sands of Btu hr Manifold and Common Vent Diameter Inches 2 308 000 7 7 6 6 6 6 6 6 3 462 000 8 8 7 7 7 6 6 6 4 616 000 9 9 9 8 8 7 7 6 Model CLN180080 THRU 199100 Input 180 000 and 199 000 Btu hr Tota...

Page 20: ...8 8 7 7 7 6 6 Number of Heaters Combined Input Btu hr 2 620 000 12 10 10 9 9 8 8 7 3 930 000 14 14 12 12 10 10 9 9 4 1 240 000 16 14 14 14 12 12 10 9 Model CLN366085 Input 366 000 btu hr Total Vent He...

Page 21: ...installation of the water piping begins 1 Water Temperature Control and Mixing Valves on page 12 2 Dishwashing Machines on page 13 3 Temperature Pressure Relief Valve on page 13 4 Closed Systems and T...

Page 22: ...inlet water connection requires an inlet dip tube refer to figure 19 The tube is supplied in the heater Follow caution labels if applying heat to this fitting Do not allow pipe dope to contact the pla...

Page 23: ...sing In this case 200 C rated wire must be used The controls of this water heater are polarity sensitive Be certain to properly wire the hot and neutral connections 24V 24V GND GND PV MV PV MV SPARK 4...

Page 24: ...e Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap must be incorporated in the piping see Figu...

Page 25: ...from faucets after extended periods of non use 1 Close the Main Gas Shutoff Valve see Figure 21 on page 24 2 Purge all air from the supply gas line up to the water heater s Main Gas Shutoff Valve 3 W...

Page 26: ...pply gas regulator as necessary Adjust the supply gas regulator s per the regulator manufacturer s instructions to achieve the required static and dynamic supply gas pressure Multiple Water Heater Ins...

Page 27: ...n off the 24vac power to the blower relay and the Ignition Control and the unit will be in standby mode until another call for heat is initiated by the thermostat See the flow chart on page 28 for mor...

Page 28: ...NO Blower power relay is energized to start blower Igni onControlprovidespowertoSpark IgniterandPilotGasValveandmonitors FlameSensortodetermineifBurnerislit 24VAC power to the Igni on Control and self...

Page 29: ...thermal expansion in a closed system See Closed Water Systems and Thermal Expansion on page 13 The Temperature Pressure Relief Valve is not intended for the constant relief of thermal expansion Temper...

Page 30: ...this manual 11 Turn on the electrical supply to place the water heater back in operation 12 Turn on the gas supply to the water heater at the Main Gas Shutoff Valve 13 Allow the water heater to compl...

Page 31: ...ut opening and scrape out any loose deposits of scale or sediment This is an economical way to avoid unnecessary usage of the deliming solution Repeat the opening and closing of the cold water inlet v...

Page 32: ...plying Teflon tape or paste to threads Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection Do not over tighten to avoid damage to threads and fittings Prepare the...

Page 33: ...ot be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the thermostat then needs to be depressed See Figure 2 for the location...

Page 34: ...blockage and or flue gas exhaust blockage Water temperature too hot Thermostat set too high Set thermostat to a lower setting Rumbling Sediment accumulation on bottom of tank Drain a quantity of water...

Page 35: ...should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TE...

Page 36: ...ostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Page 37: ...and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BAL...

Page 38: ...mp between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VA...

Page 39: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 40: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 41: ...t should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 42: ...EMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SU...

Page 43: ...VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES C...

Page 44: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Page 45: ...an the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT B...

Page 46: ...than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PO...

Page 47: ...RE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED...

Page 48: ...perature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPE...

Page 49: ...emperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE T...

Page 50: ...NOTES 50...

Page 51: ...51 NOTES...

Page 52: ...300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Service email 2tech lochinvar com www Lochinvar com Copyright 2014 Lochinvar LLC All rights reserved...

Reviews: