background image

25

PRIOR TO START UP

Installation  and  start  up  of  this  water  heater  requires  abilities 

and skills equivalent to that of a licensed tradesman in the field 

involved, see Qualifications on page 6.
Do not place the water heater in operation if any part has been 

under  water.  Immediately  call  a  qualified  service  technician  to 

inspect the water heater and to replace any part of the control 

system and any gas control which has been under water. 
Light  the  water  heater  in  accordance  with  the  Lighting  and 

Operation Instruction label on the water heater and in this manual 

on page 27.
The  water  heaters  covered  by  this  manual  are  equipped  with 

an  electronic  control  system  that  automatically  sequences  the 

Blower,  the  Igniter,  the  24  VAC  Gas  Valve,  Burner  ignition, 

and flame sensing. The control system will lock out after three 

unsuccessful ignition attempts.
Before  attempting  start  up,  thoroughly  study  and  familiarize 

yourself with the exact Sequence Of Operation, see the written 

Sequence  Of  Operation  on  page  27  and  the  Sequence  Of 

Operation Flow Chart on page 28.
Be certain that the water heater is full of water, that air is purged 

from the gas and water lines and that there are no leaks in the 

gas and water lines. Ensure all inlet water valves are open.

Filling The Water Heater

Follow these steps to fill the water heater prior to start up.
1. Close the heater drain valve.
2. Open a nearby hot water faucet to permit the air in the system 

to escape.

3. Fully open the cold water inlet valve allowing the piping and 

water heater to fill with water.

4. Close the hot water faucet opened in Step 2 as water starts to flow.

Supply Gas Line Purging

Fire or Explosion Hazard

Read instruction manual before

installing, using or servicing

water heater.

To avoid risk of fire or explosion purge discharge must not

enter into confined areas or spaces where ignition can occur.
The area must be well ventilated and all sources of ignition

must be deactivated or removed.

Gas line purging is required with new piping or systems in

which air has entered.

Use only the gas shown on the water heater rating label.
Keep ignition sources away from faucets after extended

periods of non-use.

1. Close the Main Gas Shutoff Valve, see Figure 21 on page 24.
2. Purge all air from the supply gas line up to the water heater’s 

Main Gas Shutoff Valve.

3. When all air has been purged from the supply gas line, tighten 

all supply gas line connections. 

4. Check for gas leaks, see Gas Line Leak Testing on page 24 

and repair any leaks found.

START UP

INITIAL START UP

Required Test Equipment

U-tube  manometer,  pressure  gauge,  or  digital  manometer. 

Recommended range: 20” W.C. (5 kPa).

NOTE:

  All  test  equipment  must  be  acclimated  to  ambient 

temperature before calibration and use.

Preparation

1. Adjust the thermostat to the lowest temperature setting.
2. Turn the water heater’s on/off switch to the “off” position.
3. Close the Main Gas Shut Off Valve, see Figure 21 on page 24.
4. Wait five (5) minutes for any residual gas to clear.
5. Open the Supply Gas Pressure Port on the gas control valve 

by  turning  the  center  screw  counter-clockwise.  Connect  the 

manometer to the supply gas pressure test port, see Figure 22.

6. Open the Main Gas Shutoff Valve.
7. Measure and record the supply gas pressure, this is a “static” 

supply gas pressure reading; while the water heater is not firing.

FIGURE 22. – TOP VIEW

Lighting The Water Heater

1. Turn the water heater’s on/off switch to the “on” position.

2. Adjust the thermostat to the desired water temperature.

3. Record the supply gas pressure when the 24 VAC Gas Valve is 

energized and the Burner is operating. This is a “dynamic” gas 

pressure reading; while the water heater is firing.

4. Compare  the  actual  supply  gas  pressure  reading  recorded  

above to the required minimum/maximum values given in Table 

3 on page 8. Adjust supply gas pressure as necessary, see the 

instructions that follow.

5. After the supply gas pressure adjustments are complete, turn off 

the water heater and close the Main Gas Supply Shut Off Valve. 

Disconnect the manometer from the Supply Gas Pressure Port 

and turn the center screw clockwise until the port is closed.

Supply Gas Pressure Adjustment

Fire and Explosion Hazard

Turn off gas lines during installation.
Contact a qualified installer or service

technician for installation and service.

Excessive gas pressure to gas valve can

cause serious injury or death.

Do not use water heater with any gas

other than the gas shown on the rating

label. 

Summary of Contents for CLN 120080

Page 1: ...her appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor...

Page 2: ...51 TABLE OF CONTENTS SAFE INSTALLATION USE AND SERVICE 3 APPROVALS 3 GENERAL SAFETY INFORMATION 4 Precautions 5 Grounding Instructions 5 Hydrogen Gas Flammable 5 INTRODUCTION 6 Abbreviations Used 6 Q...

Page 3: ...of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances WARNING This product contains a chemical known to the St...

Page 4: ...nce with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or service technician for...

Page 5: ...ot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCE...

Page 6: ...ything on the first few pages RE AD THE ENTIRE MANUAL BE FORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER 2 The installation must conform with these instructions and the local code authority hav...

Page 7: ...of high limit switch operation the water heater cannot be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the control then ne...

Page 8: ...307 LPH 1818 1636 1309 1212 1091 935 909 818 727 654 606 595 545 519 503 467 CLN199080 199 81 80 GPH 531 478 382 354 319 273 265 239 212 191 177 174 159 152 147 137 58 307 LPH 2009 1808 1447 1340 120...

Page 9: ...he panel must be strong enough to carry the weight of the heater when full of water A service clearance of at least 24 61 cm should be maintained from serviceable parts TABLE 4 MINIMUM CLEARANCES TO C...

Page 10: ...instruction labels from the manufacturer for placement on the blanket directly over the existing labels DO inspect the insulation blanket frequently to make certain it does not sag thereby obstructing...

Page 11: ...me circulating pumps are manufactured with sealed bearings and do not require further lubrication Some circulating pumps must be periodically oiled Refer to the pump manufacturer s instructions for lu...

Page 12: ...with all gas burning equipment running at maximum rate dynamic pressure The gas supply pressure must be stable within 1 5 W C 0 37 kPa from static to dynamic pressure to provide good performance Press...

Page 13: ...1 and Water Piping Diagrams starting on page 35 TEMPERATURE PRESSURE RELIEF VALVE Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized t...

Page 14: ...ve is not intended for the constant relief of thermal expansion A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems an...

Page 15: ...ening required to provide the free area specified Where the louver and grille design and free area are not known it shall be assumed that wood louvers will have 25 free area and metal louvers and gril...

Page 16: ...hes 300 mm of the top of the enclosure shall be provided See Figure 14 The water heater shall have clearances of at least 1 inch 25 mm from the sides and back and 6 inches l50 mm from the front of the...

Page 17: ...aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 OUTDOOR AIR THROUGH TWO VERTICAL DUCTS The illustrations shown in thi...

Page 18: ...Fuel Gas Code ANSI Z223 1 and with the Category I Venting Tables If any part of the vent system is exposed to ambient temperatures below 40 F 4 4 C it must be insulated to prevent condensation Do not...

Page 19: ...sands of Btu hr Manifold and Common Vent Diameter Inches 2 308 000 7 7 6 6 6 6 6 6 3 462 000 8 8 7 7 7 6 6 6 4 616 000 9 9 9 8 8 7 7 6 Model CLN180080 THRU 199100 Input 180 000 and 199 000 Btu hr Tota...

Page 20: ...8 8 7 7 7 6 6 Number of Heaters Combined Input Btu hr 2 620 000 12 10 10 9 9 8 8 7 3 930 000 14 14 12 12 10 10 9 9 4 1 240 000 16 14 14 14 12 12 10 9 Model CLN366085 Input 366 000 btu hr Total Vent He...

Page 21: ...installation of the water piping begins 1 Water Temperature Control and Mixing Valves on page 12 2 Dishwashing Machines on page 13 3 Temperature Pressure Relief Valve on page 13 4 Closed Systems and T...

Page 22: ...inlet water connection requires an inlet dip tube refer to figure 19 The tube is supplied in the heater Follow caution labels if applying heat to this fitting Do not allow pipe dope to contact the pla...

Page 23: ...sing In this case 200 C rated wire must be used The controls of this water heater are polarity sensitive Be certain to properly wire the hot and neutral connections 24V 24V GND GND PV MV PV MV SPARK 4...

Page 24: ...e Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap must be incorporated in the piping see Figu...

Page 25: ...from faucets after extended periods of non use 1 Close the Main Gas Shutoff Valve see Figure 21 on page 24 2 Purge all air from the supply gas line up to the water heater s Main Gas Shutoff Valve 3 W...

Page 26: ...pply gas regulator as necessary Adjust the supply gas regulator s per the regulator manufacturer s instructions to achieve the required static and dynamic supply gas pressure Multiple Water Heater Ins...

Page 27: ...n off the 24vac power to the blower relay and the Ignition Control and the unit will be in standby mode until another call for heat is initiated by the thermostat See the flow chart on page 28 for mor...

Page 28: ...NO Blower power relay is energized to start blower Igni onControlprovidespowertoSpark IgniterandPilotGasValveandmonitors FlameSensortodetermineifBurnerislit 24VAC power to the Igni on Control and self...

Page 29: ...thermal expansion in a closed system See Closed Water Systems and Thermal Expansion on page 13 The Temperature Pressure Relief Valve is not intended for the constant relief of thermal expansion Temper...

Page 30: ...this manual 11 Turn on the electrical supply to place the water heater back in operation 12 Turn on the gas supply to the water heater at the Main Gas Shutoff Valve 13 Allow the water heater to compl...

Page 31: ...ut opening and scrape out any loose deposits of scale or sediment This is an economical way to avoid unnecessary usage of the deliming solution Repeat the opening and closing of the cold water inlet v...

Page 32: ...plying Teflon tape or paste to threads Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection Do not over tighten to avoid damage to threads and fittings Prepare the...

Page 33: ...ot be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the thermostat then needs to be depressed See Figure 2 for the location...

Page 34: ...blockage and or flue gas exhaust blockage Water temperature too hot Thermostat set too high Set thermostat to a lower setting Rumbling Sediment accumulation on bottom of tank Drain a quantity of water...

Page 35: ...should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TE...

Page 36: ...ostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Page 37: ...and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BAL...

Page 38: ...mp between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VA...

Page 39: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 40: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 41: ...t should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 42: ...EMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SU...

Page 43: ...VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES C...

Page 44: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Page 45: ...an the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT B...

Page 46: ...than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PO...

Page 47: ...RE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED...

Page 48: ...perature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPE...

Page 49: ...emperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE T...

Page 50: ...NOTES 50...

Page 51: ...51 NOTES...

Page 52: ...300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Service email 2tech lochinvar com www Lochinvar com Copyright 2014 Lochinvar LLC All rights reserved...

Reviews: