11.3 CHA Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General faults and failures
Feature
Cause
Measure
Comment
Gas smell
Gas leak
Warning
Close the main gas valve at once.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Warning
Immediately contact your installation engineer or local gas
company.
Water leakage
Leakage from a water
connection (threaded)
Tighten the threaded connection
If the leak persists, consult your installation engineer
Leakage from another
nearby water water
heater or pipe segment
Trace the leak
Leakage from the water
heater tank
Consult the supplier and/or manufacturer
Condensation
Before drawing off (too much) hot tap water, wait until the water in
the heater has reached the set temperature.
Explosive ignition
Poor flame profile
Incorrect supply
pressure and/or burner
pressure
Set the correct supply pressure and/or burner
pressure.
(3.11 "Checking the supply pressure and burner
pressure")
If ignition is not improved, consult your installation engineer.
Contaminated burner
Clean the burner(s)
(12.4.2 "Clean the burner(s)")
Contaminated orifice
Clean the orifice(s)
(12.4.3 "Clean the orifice(s)")
Inadequate air supply
Improve the air supply by better ventilating the boiler room.
Summary of Contents for CHA 100 CE
Page 4: ...4 Instruction manual CHA gis...
Page 10: ...Introduction 10 Instruction manual CHA 1 gis...
Page 32: ...Installation 32 Instruction manual CHA 3 is...
Page 40: ...Conversion to a different gas category 40 Instruction manual CHA 4 is...
Page 50: ...Starting the water heater 50 Instruction manual CHA 9 gis...
Page 52: ...Shutting down 52 Instruction manual CHA 10 gis...
Page 70: ...Electrical diagram 70 Instruction manual CHA 14 is...
Page 72: ...Declaration of Conformity 72 Instruction manual CHA 15 is...