Installation
28
Instruction manual CHA
3
is
3.10.5
Weekly timer circuit
1. Cut the image of the weekly timer from the operating panel.
2. Place the weekly timer in the opening thus created.
3. Connect the cables to points 7 (N), 8 (L) and 11 (L) using wire end sheaths.
4. Connect the cable with the crimped terminal clip onto position B4 on the
ON/OFF switch.
5. If you do not need to make any more connections, then fit the protective
cover back on the control column.
3.10.6
Extra error signal ("Alarm OUT").
Alarm OUT is a potential free terminal that is switched when an error is
detected. Devices (e.g. one or more lights) can be connected to this in order to
signal the fault (max. 250V, 10A).
The device or devices may be connected in either a circuit with a make-contact
(light illuminated when there is an error) or a circuit with a break-contact (light
illuminated during normal use).
1. Feed the extra signalling cable through the metric strain relief in the top of
the control column.
2. Connect the extra signalling device to points 13 (N) and 14 (P) and/or 14 (P)
and 15 (NC) as show in the
Terminal block
.
3. Tighten the strain relief so that the cable is clamped.
4. If you do not need to make any more connections, then fit the protective
cover back on the control column.
Summary of Contents for CHA 100 CE
Page 4: ...4 Instruction manual CHA gis...
Page 10: ...Introduction 10 Instruction manual CHA 1 gis...
Page 32: ...Installation 32 Instruction manual CHA 3 is...
Page 40: ...Conversion to a different gas category 40 Instruction manual CHA 4 is...
Page 50: ...Starting the water heater 50 Instruction manual CHA 9 gis...
Page 52: ...Shutting down 52 Instruction manual CHA 10 gis...
Page 70: ...Electrical diagram 70 Instruction manual CHA 14 is...
Page 72: ...Declaration of Conformity 72 Instruction manual CHA 15 is...