Installation guide
building controls in perfection
®
Bringing into operation
requirements:
The LCN-GT10D can be operated on LCN bus modules with firmware
140719 (July 2010) or after and be parametrized with the LCN-PRO version 4.x or after.
Settings:
The
Up to 4 periphery devices may be operated parallel to the LCN-GT10D on the I-port, e.g.
LCN-GRT, -RR, -GT3L, -GT2, -GBL, however not the LCN-ULT, -GT4D or IOS-devices.
please see also ”TDI-connection of peripheries”.
When operating the LCN-GT4D/-GT10D, no DALI/DSI signals can be given
out! Operating the LCN-IV as pulse counter / counter input, is not possible! The power
supply for the LCN-GT10D must only be supplied from the LCN-NUI or the optionally
obtainable LCN-NIH .
The status messages from the LCN-GT10D reacts to older LCN modules as follows:
Serial number from sending module
retrievable information
060101 (Jan. 1996) . . . . . . . relays- / binary sensors- / sums- / output status
0A0A0B (Oct. 2000) . . . . . . . . . same as 060101, additionally: actual value
100A06 (Oct. 2006) . . . . . . . . . . same as 0A0A0B, additionally: set value
LCN-GT10D is recognized automatically from the module and the tempera-
ture is registered in the variable 4 (R1var) - you can check the value in the analogue status
window of the LCN-PRO.