LNGS.465213.270-10 OM
Page 41
EEPROM
address
Description
Possible values
10
Number of floors, equals to
0 for bridge scheme
1…31
11
Voice tract checkup is on
0- Voice tract checkup disabled; 1…99- the value of permittable quality of voice communication in percents (recommended
value is 20)
12
Out of service input
mapping
0,255- doesn't change mapping mode; 1…48- enables mapping out of service input onto the corresponding 1…48 state;
101…148- enables inverse mapping of out of service input onto the corresponding 1…48 state; 51…84- enables mapping out
of service input onto the corresponding control point; 99- enables function of control of the calls circuit order; 151...184-
enables inverse mapping out of service input onto the corresponding control point
13
Lift number in the group
14
Sound notification in cain
See Lift unit ver.7.2 Operational manual, Appendix D
18
EEPROM table usage
enabled
0-standatd table; 85-EEPROM table
83
Turning on lift on request
from the line enabled
0 – prohibited; 1 – allowed
84
Inverse bit
0 – door closed, contact open; 1 – door closed, contact closed
85
Out of service input inverse
bit
1 – voltage present; 0 – no voltage
86
Turning on at lift power on
0-yes; 1-no
87
Cabin door penetration
0-not proceed; 1-proceed
91
Bit enabling additional
messages formation
0-off; 1-on
92
Monitoring passenger in a
cabin
0-disable; 1-enable
94
Overspeed governor sensor
support
0- Disabled; 1- enabled. If Enabled, USER4 input/output is configured to exchange data with overspeed governor sensor
output, where as output OUT1 assigned to supply power. This case all previously made assignments are ignored
95
Exchange speed rate for
UKL/UL lift
0-4800; 1-6900 bps
96
Landing door indicator
mode
0-safety device only; 1-standard
97
Main drive speed
0 – 0,35-0,8 mps; 1 -0,71-1,6 mps
98
Overspeed governor sensor
type
0 – magnet; 1 - optical