LNGS.465213.270-10 OM
Page 29
Triggering intercom unit into firemen transportation mode should be made as described in Intercom unit operational
manual.
Specifying the “CALL” button contact type and intercom unit’s “FIRE” input
Upon delivery, a normall
y open contact type is set for the “Call” button and the “FIRE” input. To change the type of
contact to normally closed perform the following:
- press and hold the "Call" button on the intercom unit;
- close pins 6 and 5 of XP1 terminal of the intercom uni
t to set the normally closed type of the “Call” button of the lift
cabin; close terminals 1 and 5 of the XP1 terminal to set the normally closed type of the state of the “FIRE” input of the
intercom unit;
- supply power from the battery by connecting the XP1 terminal with jumper installed between the terminals 4 and 5;
-
wait (more than 10 sec.) for flashing of the “MODE”, “WI-FI”, “CAN” LEDs in red-green color, then release the “Call”
button on the intercom unit.