Assembly instructions | LK Minishunt M60

Technical data

Article no.

241 80 85

Max. operating pres-

sure

0,6 MPa 

Operational tempera-

ture secondary

+12 - +63 ºC 

Ambient temperature Max +35 ºC 
Circulation pump

Wilo Yonos Para RSB 15/6-RKA 

Voltage

1 phase 230 V +10%/-15% 50/60 

Hz, PE

Output

Max 45 W

Current

Max 0,44 A

Protection class

IP X4D

Insulation class

F

Valve capacity

Kvs 1,12, with self-acting thermo-

stat Kv 0,51 

Flow diagram

Diode indicator on the pump

Diode

Meaning

Note

Action

Lights green

Pump in operation.

Normal operation.

Fast flashing green

Pump is running venting routine 

during 10 min. Then, the required 

pump capacity must be set. 

Venting routine active.

Flashes red/green

The pump is ready for operation, 

but will not start. The pump starts 

automatically as soon as the error 

is no longer present.

Under- or over-voltage 

U<160 V, U>253 V.

Check the power supply 

>195 V / <253 V. 

Flashes red

The pump is not working, pump 

blocked.

The pump does not restart 

automatically.

Check the pump housing, 

if necessary replace the pump.

Diode not lit

No power supply or damaged 

electronics.

Check the power connection, cable 

connection, if necessary replace 

the pump.

Trouble shooting 

The under floor heating circuit does not 
get warm

• Check that the shut-off valves for (2) and the 

return valve (7) are open.

• Check the setting on the maximum limiter 

valve (6).

• Check the connection, operation and setting 

of the circulation pump.

If the above adjustments have been performed 

and there is still no heat reaching the under floor 

heating circuit, this can be an indication of low 

available drive pressure from the primary side. 

Begin by checking that the circulation pump of 

the primary side can be stepped up. If this does 

not rectify the situation, the circulation pump of 

the minishunt can help to ”draw” the water from 

the primary side to the under floor heating side 

by gradually closing (clockwise) the VF valve (10) 

until the correct temperature has been achieved.

Return temperature of the under floor 
heating circuit is too low

• Open the return valve (7).

• Increase the speed of the circulation pump 

using the function selector.

The radiators after the minishunt do not get 
warm for the single pipe radiator systems 

The LK Minishunt M60 is supplied in the twin 

pipe design. For the single pipe system, switching 

will need to be carried out, see heading 

Start up/

Adjustment.

SV

P

AV/RV

AV/

RV

Tmax

Primary side 

with master 

pump

Secondary side 

for underfloor 

heating

2-1 Switch for single or twin

      pipe radiator systems

Summary of Contents for Minishunt M60

Page 1: ...heating areas up to 60 m de pending on heating requirements laying proce dures etc and is connected to an existing heating system The shunt unit consists of an automatic speed controlled circulation pump for the under floor heating circuit a maximum limit function for the feed temperature a return valve for the under floor heating circuit a fill discharge and air bleed valve plus a thermostatic va...

Page 2: ... connection The minishunt s primary connection is provided with a EuroCone thread Pipe connection to the primary side is made using the enclosed fit tings for 15 mm Cu Connectors for Cu 12 mm and to PEX PAL pipes dimension 16x2 20x2 and 20x2 8 mm are available as accessories The secondary connections of the minishunt have female thread The under floor heating pipes are connected for a floor heatin...

Page 3: ...ctric LK Actuator and is installed according to the se quence below Click Assembly of supplied thermostat To install the supplied thermostat with capillary tube connected sensor dismantle the hand actua tor and the black threaded adapter according to the sequence below The capillary tube connected sensor is preferably placed on a interior wall As accessory a thermostat with 5 m capillary tube alte...

Page 4: ...adjustment should be carried out as described below If the available drive pressure and flow on the primary side are known the theoretical adjust ment for the minishunt can be calculated refer to the project planning instructions for LK Floor Heating 1 Carry out air bleeding of the floor heating system and the minishunt as shown above Installation cabinets To conceal the installation there are cab...

Page 5: ...eeds for 10 min The venting routine is indicated with a fast flashing green diode light After completing the venting process the con stant pressure curve that best matches the requirements of the system is chosen See capacity chart below 3 Set the switch 2 for single or twin pipe radiator systems twin pipe radiator sys tem is factory set at delivery For single pipe systems the outer hex screw spin...

Page 6: ... pump s automatic venting routine to remove accumulated air in the pump s rotor chamber The automatic venting routine start after 3 seconds and lasts for 10 minutes Venting routine indicated by a fast flashing green diode light After complete venting choose the constant pressure curve that best matches the re quirements of the system see capacity chart be low If no choice is made the pump operatio...

Page 7: ...y replace the pump Trouble shooting The under floor heating circuit does not get warm Check that the shut off valves for 2 and the return valve 7 are open Check the setting on the maximum limiter valve 6 Check the connection operation and setting of the circulation pump If the above adjustments have been performed and there is still no heat reaching the under floor heating circuit this can be an i...

Page 8: ...2x58m 2x69m 3x54m 3x61m 3x69m 4x58m 4x63m 4x69m 5 Clip Rail 16 c c 160 mm 1x35m 1x70m 1x105m 2x70m 2x88m 3x70m 3x82m 3x93m 4x79m 4x88m 4x96m 6 Clip Rail 20 c c 300 mm 1x19m 1x38m 1x57m 1x76m 2x48m 2x57m 2x67m 2x76m 3x57m 3x63 3x70m 3x76m 7 HeatFloor 22 pipe dim X16 c c 200 mm 1x29m 1x57m 2x43m 2x57m 2x70m 3x57m 3x67m 3x76m 4x64m 4x70m 4x78m 4x85m 8 Floor Joist Plate 16 c c 200 mm 1x29m 1x57m 2x43m...