Assembly instructions | LK Minishunt M60

Setting of the temperature limiter for the feed temperature 

of the under floor heating. 

Dial settings from open 

position

Max. temperature

0,0 

65 ºC 

0,5 

57 ºC 

1,0 

50 ºC 

1,5 

43 ºC 

2,0 

35 ºC 

Setting of the thermostat with the capillary tube connec-

ted sensor. 

Marking on thermostat

Room temperature 

8 ºC 

14 ºC 

20 ºC 

26 ºC 

32 ºC 

Circulation pump

The circulation pump has automatic speed con-

trol, which reduces power consumption and gi-

ves a quieter operation as the pump adjusts the 

flow according to the requirements of the system. 

A cast arrow on the pump housing indicates the 

direction of the flow. For under floor heating it 

is recommended that the pump is set to constant 

pressure control. Chose the constant pressure 

curve that best matches the requirements of the 

system, see capacity chart below. Ensure that the 

pump never runs dry and the system is well ven-

ted before use. Use the pump´s automatic venting 

routine at start up.

Setting the pump function selector

2.  Start the pump. Upon start up, use the auto-

matic venting routine to remove accumula-

ted air in the pump. The automatic venting 

routine starts after 3 seconds and proceeds 

for 10 min. The venting routine is indicated 

with a fast flashing green diode light. After 

completing the venting process, the con-

stant pressure curve that best matches the 

requirements of the system is chosen. See 

capacity chart below.

3.  Set the switch (2) for single or twin pipe 

radiator systems (twin pipe radiator sys-

tem is factory set at delivery). For single 

pipe systems the outer hex-screw spindle is 

gradually screwed out until correct tempe-

rature is achieved to the radiators. The inner 

hex-screw spindle must be screwed out.

For twin pipe systems the outer hex-screw 

spindle (dim. 10 mm hex.) must be screwed 

in and the inner hex-screw spindle (dim. 4 

mm hex.) screwed out. 

4.  Set the primary temperature from the hea-

ting source to the minishunt to approx. 55 

°C.

5.  Set the temperature limiter (6) as given in 

the table below. Normal setting is approx. 

50 °C.

6.  Set the thermostat (3) as given in the table 

below.

7.  Allow the system to stabilize for approx. 10 

min.

8.  The feed temperature should now be bet-

ween 35-45 °C. 
•  If the temperature is too low, see heading 

Trouble shooting

. Note that at start up a 

system in an unheated concrete slab, can 

take up to 24 hours before the feed tempe-

rature has reached the correct level. 

•  If the temperature is too high, adjust the 

feed temperature using the temperature 

limiter (6) as given in the table below.

9.  Finish off by resetting the primary tempera-

ture to normal temperature.

Summary of Contents for Minishunt M60

Page 1: ...heating areas up to 60 m de pending on heating requirements laying proce dures etc and is connected to an existing heating system The shunt unit consists of an automatic speed controlled circulation pump for the under floor heating circuit a maximum limit function for the feed temperature a return valve for the under floor heating circuit a fill discharge and air bleed valve plus a thermostatic va...

Page 2: ... connection The minishunt s primary connection is provided with a EuroCone thread Pipe connection to the primary side is made using the enclosed fit tings for 15 mm Cu Connectors for Cu 12 mm and to PEX PAL pipes dimension 16x2 20x2 and 20x2 8 mm are available as accessories The secondary connections of the minishunt have female thread The under floor heating pipes are connected for a floor heatin...

Page 3: ...ctric LK Actuator and is installed according to the se quence below Click Assembly of supplied thermostat To install the supplied thermostat with capillary tube connected sensor dismantle the hand actua tor and the black threaded adapter according to the sequence below The capillary tube connected sensor is preferably placed on a interior wall As accessory a thermostat with 5 m capillary tube alte...

Page 4: ...adjustment should be carried out as described below If the available drive pressure and flow on the primary side are known the theoretical adjust ment for the minishunt can be calculated refer to the project planning instructions for LK Floor Heating 1 Carry out air bleeding of the floor heating system and the minishunt as shown above Installation cabinets To conceal the installation there are cab...

Page 5: ...eeds for 10 min The venting routine is indicated with a fast flashing green diode light After completing the venting process the con stant pressure curve that best matches the requirements of the system is chosen See capacity chart below 3 Set the switch 2 for single or twin pipe radiator systems twin pipe radiator sys tem is factory set at delivery For single pipe systems the outer hex screw spin...

Page 6: ... pump s automatic venting routine to remove accumulated air in the pump s rotor chamber The automatic venting routine start after 3 seconds and lasts for 10 minutes Venting routine indicated by a fast flashing green diode light After complete venting choose the constant pressure curve that best matches the re quirements of the system see capacity chart be low If no choice is made the pump operatio...

Page 7: ...y replace the pump Trouble shooting The under floor heating circuit does not get warm Check that the shut off valves for 2 and the return valve 7 are open Check the setting on the maximum limiter valve 6 Check the connection operation and setting of the circulation pump If the above adjustments have been performed and there is still no heat reaching the under floor heating circuit this can be an i...

Page 8: ...2x58m 2x69m 3x54m 3x61m 3x69m 4x58m 4x63m 4x69m 5 Clip Rail 16 c c 160 mm 1x35m 1x70m 1x105m 2x70m 2x88m 3x70m 3x82m 3x93m 4x79m 4x88m 4x96m 6 Clip Rail 20 c c 300 mm 1x19m 1x38m 1x57m 1x76m 2x48m 2x57m 2x67m 2x76m 3x57m 3x63 3x70m 3x76m 7 HeatFloor 22 pipe dim X16 c c 200 mm 1x29m 1x57m 2x43m 2x57m 2x70m 3x57m 3x67m 3x76m 4x64m 4x70m 4x78m 4x85m 8 Floor Joist Plate 16 c c 200 mm 1x29m 1x57m 2x43m...

Reviews: