26
D2. Diagnostic Menu
Hold down the mode button for ≈ 10 seconds from the global screen to access the diagnostic
menu.
Dia
g
Menu
E x it
Use
or
to select from the following options , then press
SET
to view the status:
CoilTem
p
Line1:
In=36.0°c
(Indoor coil sensor)
Line2:
Out=34.0°c
(Outoor coil sensor)
Com
p
Load
Line1:
In=36.0°c
(Indoor coil sensor)
Line2:
LD=100%
(Compressor load)
Defrost
Line1:
Defrost=
Line2:
Ok
, or
DeIce
, or
DeWater
.
3 Phase
Line1(scrolls):
L1=Ok L2=Down L3=Down
(state can be
Down
or
Ok
, this example
is single phase)
Line2(scrolls):
Health=
(either
Bad/Not 3Phase
, or
Ok
)
HP/LP/DI
(DI=Discharge sensor)
Line1(scrolls):
HP=Ok LP=Ok
(either
Ok
or
Fault
)
Line2:
Di=70.0°c
NOTE: Discharge sensor temperatures below 70.0 °C will be displayed as 70.0 °C.