MP8000 Programming Guide

8

Fault Record Retrieval

There are two methods of requesting a fault record: By index, and by date. (See Table 6)

To request fault records by Index:

1.   Write the fault index to the FRI register (0x300). Note, this index is zero based, so the most recent fault 

record will have an index of zero. 

a. Also the maximum valid index is 1023

2.  Write to the CMD register (0x0076) with command 0x11 (see Table 4)
3.  Continuously read the FRI register until it has been updated to 0xFFFF
4.  The fault record is ready to read, starting at address 0x0308. (see Table 6)

To request fault records by date:

1.  Write zero to the FRI register (0x0300).
2.  Write the UNIX (32bit) time stamp to the FRO register (0x0304). 

  a. The log entry with the next earlier time entry will be retrieved.
3.  Write to the CMD register (0x0076) with command 0x11 (see Table 4)
4.  Continuously read the FRI register until it has been updated to 0xFFFF
5.  The fault record is ready to read, starting at address 0x0308. (see Table 6)

Table 6 - Fault Record Retrieval

FIELD 

NAME

MODBUS REGISTER

DESCRIPTION

FORMAT

PERMISSION

ADDRESS HEX

ADDRESS 

DECIMAL

SIZE

FRI

0x0300

768

2

Fault Request Index (Or base DT)

C

W

FRO

0x0302

770

2

Fault Request Offset

F

W

FCODE

0x0304

772

2

Fault Code indicating the source of the fault

B

R

FDT

0x0306

774

2

Date Time of Fault

K

R

V1F

0x0308

776

2

Measured line 1 Voltage RMS

H

R

V2F

0x030A

58

2

Measured line 2 Voltage RMS

H

R

V3F

0x030C

780

2

Measured line 3 Voltage RMS

H

R

I1F

0x030E

782

2

Measured line 1 Current RMS

H

R

I2F

0x0310

784

2

Measured line 2 Current RMS

H

R

I3F

0x0312

786

2

Measured line 3 Current RMS

H

R

MRTF

0x0314

788

2

Time since motor started

H

R

TCUF

0x0316

790

2

Thermal Capacity Used

L

R

P1F

0x0318

792

2

Measured line 1 Power

C

R

P2F

0x031A

794

2

Measured line 2 Power

C

R

P3F

0x031C

796

2

Measured line 3 Power

C

R

PF1F

0x031E

798

1

Measured line 1 Power Factor

P

R

PF2F

0x031F

799

1

Measured line 2 Power Factor

P

R

PF3F

0x0320

800

1

Measured line 3 Power Factor

P

R

IGFF

0x0321

801

2

Ground Fault Current

H

R

VUBF

0x0323

803

1

Measured Voltage Unbalance

G

R

CUBF

0x0324

804

1

Measured Current Unbalance

G

R

FAF

0x0325

805

1

Frequency Measured from Phase A

G

R

SEQF

0x0326

806

1

Measured Phase Sequence

G

R

FSDF

0x0327

807

5

Fault Specific Data

N.A

R

© 2018 Littelfuse Protection Relays & Controls 

www.littelfuse.com/mp8000

Summary of Contents for MP8000

Page 1: ...MP8000 Programming Guide MODBUS TCP and Ethernet IP Software Development Guide Patent Pending 2018 Littelfuse Protection Relays Controls www littelfuse com mp8000 MP8000...

Page 2: ...resses 3 MP8000 MODBUS MEMORY MAP 3 CONFIGURATION SETTINGS 4 Command Register 6 Real Time Status 7 Fault Record Retrieval 8 MP8000 ETHERNET IP INTERFACE 10 MP8000 Network Settings 10 RSLOGIX5000 Setup...

Page 3: ...evices and initiate a request for data or to issue a command to the Model MP8000 to stop or reset the Model MP8000 s control relay When the Model MP8000 responds with the requested data or confirmatio...

Page 4: ...first holding register The address numbering system is defined in the standard to describe the message that is actually sent to the physical communications bus By starting the addresses at 0 rather th...

Page 5: ...rd at 0019 00 L2 L3 476 7 Low Byte of Word at 0019 00 6 High Byte of Word at 001A 01 7 Low Byte of Word at 001A DC 8 High Byte of Word at 001B 00 L3 L1 483 9 Low Byte of Word at 001B 00 8 High Byte of...

Page 6: ...ay 3 L R W RU 0x001B 27 1 1 Restart Attempts for Undercurrent Trips B R W RF 0x001C 28 1 1 Restart Attempts for all other faults B R W GF 0x001D 29 2 0 Ground Fault Current Threshold H R W GFTD 0x001F...

Page 7: ...will be disabled Reserved 3 0x0008 Reserved 4 0x0010 Single Phase Motor 5 0x0020 Single phase motor operation 3 Phase w 1 Volt 6 0x0040 3phase motor with single voltage PT Reserved 7 0x0080 Reserved 8...

Page 8: ...n 0x0009 CMD_MOTOR_RESTART Attempt to Restart the Motor 0x0010 CMD_RESET_MOTOR_SERVICE_TIME Reset Motor Service time to NOW 0x0011 CMD_FAULT_LOOKUP Fault Lookup From FIDX and FRO Modbus only 0x0012 CM...

Page 9: ...d Line Frequency G R SEQ 0x0210 528 1 Measured Phase Sequence B R VUBM 0x0211 529 1 Measured Voltage Unbalance G R CUBM 0x0212 530 1 Measured Current Unbalance G R V1 0x0213 531 2 Measured line 1 Volt...

Page 10: ...N ADDRESS HEX ADDRESS DECIMAL SIZE FRI 0x0300 768 2 Fault Request Index Or base DT C W FRO 0x0302 770 2 Fault Request Offset F W FCODE 0x0304 772 2 Fault Code indicating the source of the fault B R FD...

Page 11: ...0x00000200 10 2 0 17 12 RMTF Tripped triggered from remote source 0x00000400 11 2 0 17 12 LIN Tripped on Linear Overcurrent 0x00000800 12 2 0 17 12 STALL Tripped Motor Stall 0x00001000 13 2 0 17 12 A...

Page 12: ...Sequence Holdoff 0x00080000 103 UNDEFF Undefined Holdoff 0x00100000 N A GFALARM Ground Fault Alarm 0x00800000 16 MP8000 ETHERNET IP INTERFACE MP8000 Network Settings By default the MP8000 is configure...

Page 13: ...y series 8000 UINT 4 Revision Get Major revision must match the eds value Major Minor 3 002 UINT 7 Product Name Get Human readable identification MP8000 SHORT_STRING Assembly Object ATTRIBUTE NUMBER A...

Page 14: ...tart Attempts for Undercurrent Trips R W UINT 1 18 RF Restart Attempts for all other faults R W UINT 1 19 GF Ground Fault Current Threshold R W UDINT 0 20 GFTD Ground Fault Trip Delay R W UINT 50 21 G...

Page 15: ...red Current Unbalance R UINT 14 V1 Measured line 1 Voltage RMS R UDINT 15 V2 Measured line 2 Voltage RMS R UDINT 16 V3 Measured line 3 Voltage RMS R UDINT 17 I1 Measured line 1 Current RMS R UDINT 18...

Page 16: ...CIFICATIONS Protocol EtherNet IP Ports 1 IP Address 1 Number of Connections 1 Connection Connector RJ45 Cable CAT5 Length 100 m 328 Interface 10BASE T 100BASE Tx 2018 Littelfuse Protection Relays Cont...

Reviews: