MP8000 Programming Guide
8
Fault Record Retrieval
There are two methods of requesting a fault record: By index, and by date. (See Table 6)
To request fault records by Index:
1. Write the fault index to the FRI register (0x300). Note, this index is zero based, so the most recent fault
record will have an index of zero.
a. Also the maximum valid index is 1023
2. Write to the CMD register (0x0076) with command 0x11 (see Table 4)
3. Continuously read the FRI register until it has been updated to 0xFFFF
4. The fault record is ready to read, starting at address 0x0308. (see Table 6)
To request fault records by date:
1. Write zero to the FRI register (0x0300).
2. Write the UNIX (32bit) time stamp to the FRO register (0x0304).
a. The log entry with the next earlier time entry will be retrieved.
3. Write to the CMD register (0x0076) with command 0x11 (see Table 4)
4. Continuously read the FRI register until it has been updated to 0xFFFF
5. The fault record is ready to read, starting at address 0x0308. (see Table 6)
Table 6 - Fault Record Retrieval
FIELD
NAME
MODBUS REGISTER
DESCRIPTION
FORMAT
PERMISSION
ADDRESS HEX
ADDRESS
DECIMAL
SIZE
FRI
0x0300
768
2
Fault Request Index (Or base DT)
C
W
FRO
0x0302
770
2
Fault Request Offset
F
W
FCODE
0x0304
772
2
Fault Code indicating the source of the fault
B
R
FDT
0x0306
774
2
Date Time of Fault
K
R
V1F
0x0308
776
2
Measured line 1 Voltage RMS
H
R
V2F
0x030A
58
2
Measured line 2 Voltage RMS
H
R
V3F
0x030C
780
2
Measured line 3 Voltage RMS
H
R
I1F
0x030E
782
2
Measured line 1 Current RMS
H
R
I2F
0x0310
784
2
Measured line 2 Current RMS
H
R
I3F
0x0312
786
2
Measured line 3 Current RMS
H
R
MRTF
0x0314
788
2
Time since motor started
H
R
TCUF
0x0316
790
2
Thermal Capacity Used
L
R
P1F
0x0318
792
2
Measured line 1 Power
C
R
P2F
0x031A
794
2
Measured line 2 Power
C
R
P3F
0x031C
796
2
Measured line 3 Power
C
R
PF1F
0x031E
798
1
Measured line 1 Power Factor
P
R
PF2F
0x031F
799
1
Measured line 2 Power Factor
P
R
PF3F
0x0320
800
1
Measured line 3 Power Factor
P
R
IGFF
0x0321
801
2
Ground Fault Current
H
R
VUBF
0x0323
803
1
Measured Voltage Unbalance
G
R
CUBF
0x0324
804
1
Measured Current Unbalance
G
R
FAF
0x0325
805
1
Frequency Measured from Phase A
G
R
SEQF
0x0326
806
1
Measured Phase Sequence
G
R
FSDF
0x0327
807
5
Fault Specific Data
N.A
R