© 2018 Littelfuse Fresh Water Pumping
Littelfuse.com/Pump-Protection
30
Three-Phase Pump Protection
Fully Programmable
Table 9: Wiring Configuration for 777-LR-P2 & 777-LR-KW/HP-P2 Based on Motor Full Load Amps
RECOMMENDED FULL LOAD AMPS
OC RANGE
(AMPS)
UC RANGE
(AMPS)
# OF PASSES THROUGH
EACH WINDOW
MULT
(CT RATIO)
1.0-2.0
1.0-5.0
0, 0.5-4.9
2
2
2.1-9.0
2.0-10.0
0, 1-9.8
1
1
10-25
10-50
0, 5-49
2
25 (50:5)
20-50
20-100
0, 10-98
1
50 (50:5)
30-75
30-150
0, 15-147
1
75 (75:5)
40-100
40-200
0, 20-196
1
100 (100:5)
60-150
60-300
0, 30-294
1
150 (150:5)
80-200
80-400
0, 40-392
1
200 (200:5)
120-300
120-600
0, 60-588
1
300 (300:5)
160-400
160-800
0, 80-784
1
400 (400:5)
200-500
200-999
0, 100-980
1
500 (500:5)
240-600
240-999
0, 120-999
1
600 (600:5)
280-700
280-999
0, 140-999
1
700 (700:5)
320-800
320-999
0, 160-999
1
800 (800:5)
Table 10: Wiring Configuration for 777-MLR-KW/HP-P2 Based on Motor Full Load Amps
RECOMMENDED FULL LOAD AMPS
OC RANGE
(AMPS)
# OF PASSES THROUGH
EACH WINDOW
MULT
(CT RATIO)
0.5-2.10
0.5-2.7
10
10
0.5-2.3
0.5-3
9
9
0.6-2.6
0.6-3.3
8
8
0.7-3
0.7-3.8
7
7
0.8-3.5
0.8-4.5
6
6
1-4.25
1-5.4
5
5
1.2-5.25
1.2-6.7
4
4
1.6-7
1.6-9
3
3
2.5-10.5
2.5-13.5
2
2
5-21
5-27
1
1
40-90
20-108
5
100 (100:5)
60-135
30-162
5
150 (150:5)
80-180
40-216
5
200 (200:5)
120-270
60-324
5
300 (300:5)
160-360
80-432
5
400 (400:5)
200-450
100-540
5
500 (500:5)
240-540
120-648
5
600 (600:5)
270-630
140-756
5
700 (700:5)
320-740
160-864
5
800 (800:5)
777-P2 / 777-KW/HP-P2 SERIES INSTALLATION INSTRUCTIONS