OVER VIEW
Fire resistance classification according to EN 13501-3-2009
EI 180 S
(500 Pa)
EI 120 S
(500 Pa)
EI 90 S
(500 Pa)
EI 60 S
(500 Pa)
EI 30 S
(500 Pa)
Rigid w
all
EI 120 S Installation within vertical rigid wall
Wall minimum thickness 100 mm
Wall minimum density 500 kg/m³
Mortar or plaster putty sealing
ve (i
↔
o)
W
-
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
EI 120 S Installation within vertical rigid wall
Wall minimum thickness 100 mm
Wall minimum density 500 kg/m³
Plasterboard and rock wool 100 kg/m³ sealing
ve (i
↔
o)
D
-
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
EI 180 S Installation within vertical rigid wall
Wall minimum thickness 140 mm
Wall minimum density 500 kg/m³
Mortar sealing
ve (i
↔
o)
W
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
Fle
xible w
all
EI 120 S Installation within vertical light wall (plasterboard)
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Mortar or plaster putty sealing
ve (i
↔
o)
W
-
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
EI 90 S Installation within vertical light wall (plasterboard)
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Plasterboard and rock wool 100 kg/m³ sealing
ve (i
↔
o)
D
-
-
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
EI 120 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i
↔
o)
W
-
B X H
min 200 X 200
max 1000 X 600
B X H
min 200 X 200
max 1000 X 600
B X H
min 200 X 200
max 1000 X 600
B X H
min 200 X 200
max 1000 X 600
EI 90 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum thickness 70 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i
↔
o)
W
-
-
B X H
min 200 X 200
max 1000 X 600
B X H
min 200 X 200
max 1000 X 600
B X H
min 200 X 200
max 1000 X 600
Floor
EI 180 S Installation within floor
Floor minimum thickness 140 mm
Floor minimum density 2200 kg/m³
Mortar sealing
ho (i
↔
o)
W
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
EI 120 S Installation within floor
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i
↔
o)
W
-
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
EI 90 S Installation within floor
Floor minimum thickness 100 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i
↔
o)
W
-
-
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H
min 200 X 200
max 1500 X 800
B X H are fire damper minimum and maximum nominal dimensions (base x height) in mm
ve
Vertical installation
ho
Horizontal installation
(i
↔
o) Origin of fire irrelevant
Pa
Pascal of depression
E Integrity
I
Thermal insulation
S
Smoke seal
W
Wet method sealing
D
Dry method sealing
Cert. N° 1812-CPR-1006 EN 15650