16
/17
Fire resistance classification
Hole size “D1 x D2”
[mm]
Damper protrusion from
the wall “E”
[mm]
Wall minimum thickness “S”
[mm]
Sealing
Rigid w
all
EI 120 S Installation within rigid vertical wall with Fire Batt (Weichschott) sealing
Wall minimum density 500
kg/m³
EI 90 S
(300 Pa)
(B+800 max) x (H+800
max)
205
100
Rock wool 140 kg/
m³ and endothermic
varnish sealing
Fle
xible w
all
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall rock wool density up to 100
kg/m³ (optional)
EI 90 S
(300 Pa)
(B+800 max) x (H+800
max)
205
100
Rock wool 140 kg/
m³ and endothermic
varnish sealing
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall minimum density 995
kg/m³
EI 90 S
(300 Pa)
(B+800 max) x (H+800
max)
205
100
Rock wool 140 kg/
m³ and endothermic
varnish sealing
B
Nominal base of the damper
H
Nominal height of the damper
D1 Hole base indicated in the table
D2 Hole height indicated in the table
E Damper protrusion from the wall indicated in the table
1. Rock wool panel 50 mm thick with 140 kg/m³ density.
2. PROMASTOP E PASTE or HILTI CFS-S ACR type sealant
3. PROMASTOP E PASTE or HILTI CFS-CT endothermic varnish
Installation within floor with Fire Batt (Weichschott) sealing
Refer to the section for further information.
Comply with the minimum distances indicated on section Minimum
distances
Floor opening
A opening must be provided in the floor as indicated in the table
and in the drawing
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
Filling
Fill the space between the damper and the floor using Fire Batt
(Weichschott) sealing made from two rock wool panels with mini-
mum thickness of 50 mm and minimum density of 140 kg/m³.
The panels must be covered on both faces of the wall with endo-
thermic varnish type PROMASTOP E PASTE or HILTI CFS-CT (mini-
mum thickness of 1 mm) and with an internal perimeter sealant type
PROMASTOP E PASTE or HILTI CFS-S ACR (minimum thickness of 1
mm).
Fire resistance classification
Hole size “D1 x D2”
[mm]
Damper protrusion from
the wall “E”
[mm]
Floor minimum thickness “S”
[mm]
Sealing
EI 120 S Installation within floor and Fire Batt (Weichschott) sealing
Floor minimum density 650 kg/m³
EI 120 S
(300 Pa)
(B+800 max) x (H+800
max)
205
150
Rock wool 140 kg/
m³ and endothermic
varnish sealing
B
Nominal base of the damper
H
Nominal height of the damper