17
Lindab reserves the right to make changes without prior notice
2020-08-05
UltraLink Controller
FTCU
lindab | we simplify construction
Analog out settings via modbus
Analog out is always active but you need to specify what kind of data you want to read on the
two ports;
1. Configure registers 4×401 and 4×431 for the variables you want to read on the analog out
terminals (0 = Flow, 1 = Temperature, 2 = Damper position).
2. Configure registers 4×400 and 4×430 for analog out level configuration ( (0) 0-10V, (1) 10-0V,
(2) 2-10V, (3) 10-2V)
3. Configure registers 4×401–409 and 4×431–439 with relevant data for max and min levels
for the voltage range selected in step 2. You only need to configure the max and min values
corresponding to the variable selected in step 1.
Size Ø
[mm]
4x400
Level
Conf.
4x401
Unit
Conf.
4x402
Temp Min
[°C]
4x403
Temp Max
[°C]
4x404
Flow Min
[l/s]
4x406
Flow Max
[l/s]
4x408
Angle Min
[%] *)
4x409
Angle Max
[%] *)
100
2 (2-10V)
0 (Flow)
0
50
0
55
0
100
125
0
50
0
86
0
100
160
0
50
0
141
0
100
200
0
50
0
220
0
100
250
0
50
0
344
0
100
315
0
50
0
546
0
100
400
0
50
0
880
0
100
500
0
50
0
1374
0
100
630
0
50
0
2182
0
100
*) 0% means fully closed damper position and 100% means fully open damper position.
Size Ø
[mm]
4x430
Level
Config
4x431
Unit
Conf.
4x432
Temp Min
[°C]
4x433
Temp Max
[°C]
4x434
Flow Min
[l/s]
4x436
Flow Max
[l/s]
4x438
Angle Min
[%] *)
4x439
Angle Max
[%] *)
100
2 (2-10V)
2 (Angle)
0
50
0
55
0
100
125
0
50
0
86
0
100
160
0
50
0
141
0
100
200
0
50
0
220
0
100
250
0
50
0
344
0
100
315
0
50
0
546
0
100
400
0
50
0
880
0
100
500
0
50
0
1374
0
100
630
0
50
0
2182
0
100
Default values for the relevant registers related to “Analog Out 2” are according to the table below (Default values for flow
max corresponds to 7 m/s).
PLEASE LOOK IN THE APPENDED MODBUS REGISTER FOR INSTRUCTIONS ON HOW TO CHANGE REGISTER
VALUES. SOME VALUES HAS SCALE FACTORS AND SOME VALUES OCCUPY TWO REGISTERS!
*) 0% means fully closed damper position and 100% means fully open damper position.