13
Installation instructions
Plexus
We reserve the right to make changes
2019-06-20
lindab | we simplify construction
We reserve the right to make changes
2019-06-20
4.1.5 Additional Lindab accessories for water
connections
Valves and fittings
Lindab TTR and TTV water valves
The Lindab TTR and TTV valves must be used with all
standard application chilled beams, radiant panels and
facade units. The TTR
and TTV valves ensures
easy and fast installation
thanks to the simple yet
effective Tectite push-on
connections.
For further information, please see
water
valves documentation.
Ballorex Dynamic
For application in systems where pressure alterations
may occur, the Ballorex Dynamic ensures an easy and
precise dynamic flow regulation.
Further information on request.
Push on valve with air vent
(aerator)
If a waterborne unit is mounted
in a location where issues with
build up air may occur, appling
an aerator is recommendable.
As our aerators comes coplete
with Tectite fittings, installation is done in mere seconds.
Order no: 647690 (12mm)
Ballofix valves
For easy closing off water con-
nection pipes (available with or
without handle).
Order no: 642663 / 642662
(without handle, 12mm)
For more details see:
Valves and Actuators installation
When actuator and valves are ordered together with
the Plexus and other Regula components, the cables
are pre-connected to the Connect card / Secura
from factory - (depending on your chosen solution).
The actuator and valve is taped to the side of the Plexus
and has to be connected to the correct water-pipe, tur-
ning the right way.
Example
Push on valve with Actuator installed on the battery’s
cold water outlet.
Valve arrow indicator must point in same direction as
arrow on beam pipe label.
Actuators
The actuator is a thermoelectric
actuator for opening and closing
valves on heating circuit distribu-
tors of concealed floor heating
and cooling systems. Features, as
protection in case of leaky valves,
compact and modern casing, ver-
sions in normally closed and nor-
mally open, valve adapter concept
and an enhanced life time makes
the actuator competitive and flexible. The actuator is
controlled by a room thermostat with two-point output or
pulse-width modulation.
See