TIMER OPERATION
The Off timer begins accumulating time when the ignition
switch closes. When the Off timer reaches the preset value
the pump will turn on. The pump remains activated for the
period of time that is preset on the On timer.
When the ignition switch opens the Off timer will retain its
accumulated time for a period of five days. When the ignition
switch closes during the five day period, the Off timer will
resume timing from the accumulated time it reached prior
to the ignition switch opening. If ignition switch is not closed
before the end of five day period, timer will begin with an On
period.
Remove Sealing Plug to access manual lube switch, timer
adjustments or to view the system LED’s .
Off-Time Rotary
Switch Setting
Interval Between
Lube Cycles
On-Time Rotary
Switch Setting
Pump will run
for:
0
Will not run
0
Will not run
1
1 hour
1
2 minutes
2
2 hours
2
4 minutes
3
3 hours
3
6 minutes
4
4 hours
4
8 minutes
5
5 hours
5
10 minutes
6
6 hours
6
12 minutes
7
7 hours
7
14 minutes
8
8 hours
8
16 minutes
9
9 hours
9
18 minutes
A
10 hours
A
20 minutes
B
11 hours
B
22 minutes
C
12 hours
C
24 minutes
D
13 hours
D
26 minutes
E
14 hours
E
28 minutes
F
15 hours
F
30 minutes
1. The LED marked “battery” lights when power is
applied to the PC board.
2. The LED marked “motor’’ lights when pumping
lubricant.
3. Depressing pushbutton for 2 seconds will initiate a
manual lube event.
4. Off time rotary switch. Can be adjusted to 15 values
(see chart below).
5. On time rotary switch. Can be adjusted to 15 values
(see chart below).
IMPORTANT: Do Not use the Zero position located on
the Off time and On time switches.
17