IGNITION CONTROL
NOTE:
When replacing Johnson Controls, G-60 or G-65 Ignition Control with the new
Honeywell Ignition control, the 24 VAC burner transformer (rated at 20VA) must be
replaced with the larger (rated at 40VA) #369531 Transformer.
1.
Read all instructions supplied in kit before starting.
Tools required: Center punch and 7/32" drill bit.
2.
Shut off power at main breaker.
3.
Remove control panel top and front panel.
4.
Remove front panel.
5.
Remove ignition control package from Johnson gas valve and discard.
The white flame sensor wire, from the burner to terminal #4 on Johnson gas control
is no longer used. Cut Wire at burner and discard.
NOTE: On some Impinger ovens, it may be necessary to drill the mounting holes through the
oven specification plate. Use care to avoid drilling through any important
information or agency approval markings on the specification plate.
6.
Use template supplied to locate and drill two (2) 7/32" mounting holes for new Ignition
Control. When mounting new ignition control, make certain that the green #67 ground
wire (supplied) is installed properly.
7.
Connect wiring as follows:
Connect blue wire from gas valve to terminal marked P.V. on ignition control.
Connect black wire from gas valve to termainal marked M.V./P.V. on ignition control.
Connect red wire from gas valve to terminal marked M.V. on ignition control.
Connect white wire from indicator light to ground, by using splice connection on green
wire supplied.
Connect orange spark lead from burner to terminal marked "spark" on ignition control.
NOTE: It may be necessary to replace ignition cable terminal with .250" quick-
connect terminal (supplied).
Connect the red wire from burner blower motor centrifugal switch to terminal marked
24V on ignition control.
Connect green #68 wire (supplied) from terminal 24 GND to terminal GND (burner)
to ground.
Connect the green wire from 24VAC transformer to wire #68 at terminal marked
24V(GND) on ignition control.
The Honeywell ignition control module provides 100% safety lockout. Control will try for
ignition for 15 seconds. If ignition does not occur, control will lockout or shut off. To
reset control, the burner switch must be turned off for 1 minute.
Summary of Contents for Impinger 1002
Page 12: ...Impinger I 1000 Series Service Manual International 12 SCHEMATIC 1002 1003...
Page 13: ...Impinger I 1000 Series Service Manual International 13 SCHEMATIC 1006 TO SERIAL NUMBERS Q14279...
Page 14: ...Impinger I 1000 Series Service Manual International 14 SCHEMATIC 1028 1029 S N Q19071 BELOW...
Page 15: ...Impinger I 1000 Series Service Manual International 15 SCHEMATIC 1028 1029 S N Q19078 ABOVE...
Page 16: ...Impinger I 1000 Series Service Manual International 16 SCHEMATIC 1030 TO S N Q17170...
Page 17: ...Impinger I 1000 Series Service Manual International 17 SCHEMATIC 1030 S N Q17171 ABOVE...
Page 18: ...Impinger I 1000 Series Service Manual International 18 SCHEMATIC 1032 S N Q19077 BELOW...
Page 19: ...Impinger I 1000 Series Service Manual International 19 SCHEMATIC 1032 S N Q19078 ABOVE...
Page 20: ...Impinger I 1000 Series Service Manual International 20 SCHEMATIC 1033 1034 1046 1047...
Page 21: ...Impinger I 1000 Series Service Manual International 21 SCHEMATIC 1042 1043 S N Q14279 BELOW...
Page 22: ...Impinger I 1000 Series Service Manual International 22 SCHEMATIC 1042 1043 S N Q14280 ABOVE...
Page 23: ...Impinger I 1000 Series Service Manual International 23 SCHEMATIC 1228 1229 S N Q14790 BELOW...
Page 24: ...Impinger I 1000 Series Service Manual International 24 SCHEMATIC 1228 1229 S N Q14791 ABOVE...
Page 25: ...Impinger I 1000 Series Service Manual International 25 SCHEMATIC 1242 1243...
Page 81: ...Impinger I 1000 Series Service Manual International 81 BLOW UP 1000 1200 GENERAL...
Page 83: ...Impinger I 1000 Series Service Manual International 83 BLOW UP 1002 1003 S N 2584 TO 4389...
Page 85: ...Impinger I 1000 Series Service Manual International 85 BLOW UP 1002 1003 S N 4390 ABOVE...
Page 87: ...Impinger I 1000 Series Service Manual International 87 BLOW UP 1006...
Page 89: ...Impinger I 1000 Series Service Manual International 89 BLOW UP 1028 1029 1032...
Page 91: ...Impinger I 1000 Series Service Manual International 91 BLOW UP 1030...
Page 93: ...Impinger I 1000 Series Service Manual International 93 BLOW UP 1042 1043...
Page 95: ...Impinger I 1000 Series Service Manual International 95 BLOW UP 1033 1034 1046 1047...
Page 97: ...Impinger I 1000 Series Service Manual International 97 BLOW UP 1228 1229...
Page 99: ...Impinger I 1000 Series Service Manual International 99 BLOW UP 1242 1243...
Page 101: ...Impinger I 1000 Series Service Manual International 101 BLOW UP OVEN BACK GAS...
Page 103: ...Impinger I 1000 Series Service Manual International 103 BLOW UP OVEN BACK ELECTRIC...
Page 107: ...Impinger I 1000 Series Service Manual International 107 BLOW UP SERIES 1000 CONVEYOR...
Page 109: ...Impinger I 1000 Series Service Manual International 109 BLOW UP SERIES 1200 CONVEYOR CONTROL...
Page 111: ...Impinger I 1000 Series Service Manual International 111 BLOW UP SERIES 1200 CONVEYOR...
Page 112: ...Impinger I 1000 Series Service Manual International 112...