CHIMNEY OR FLUE
•
The chimney or flue should have the following characteristics:
−
It’s advisable to read, follow and respect what indicated in the paragraphe 1.1
−
Good sel of combustion products, impermeable and completely insulated as
normative condiction
−
The flue has to be built with raw material suitable for normal mechanical stress,
warmth, action of combustion products and its condenses
−
The flow has to be vertical with deflections no hihgher that 45°
−
A right distance from combustible or flammable material, insulated with an air
cavity or right insulator
−
Internal round section, the square or rectangular section should have round corner
with a ray not less than 20 mm
−
Internal section should be constant, free and indipendent
−
Rectangluar section with sides ration max of 1,5
−
All manufacturer instruction should be respected concerning the section and the
building characteristic of the chimney or flue. For particular section, deviation of
section or path it will be necessary a complete inspection of exhaust fumes system.
−
It‘s advisable that the flue should be supplied by a „chamber „ for solid material and
condenses collection, placed under the flue throat and easy to reach and to open. It
should be also supplied by a completely seal „little door“ for inspection.
−
In case of fire of chimney or flue, employ the right system to soffocate the flames
and call for firefighter.
−
The chimney and gas tubes should be easy to log on for every maintenance and
cleaning operation.
EQUIPMENT CONNECTION TO FLUE AND EVACUATION OF COMBUSTION
PRODUCTS
•
It’s advisable to read, follow and respect what indicated in the paragraphe 1.1
•
The flue should receive the exhaust fumes from an only heating equipment
•
It’s possible to realise an equipment composed from chimney and cooking oven with an
only exhaust fumes point head the chimney, for which the manufactures has to provide
the building characteristics of exhaust fumes channel
•
It’s prohibited to connect in the same flue, the heating equipment and the suction hood
•
It’s prohibited to connect the exhaust pipe head closed space even if it is in open air
•
The direct exhaust fumes has to be done ahead roof and the exhaust pipe should have the
above characteristics.
•
Horizontal tubes connection should have a min slope steep of 3% .
•
The gas tubes should be sealed against combustion products, in case of outside passage it
should be insulated.
•
The chimney and gas tubes should be easy to log on for every maintenance and cleaning
operation.