background image

READ AND WRITE

Parameter and diagnostic data

On the IO-Link master, there are standard IO-Link parameters available such as e.g. Product ID and firmware revi-
sion. There are also LINAK specific parameters available. These include configuration of the beaviour in outwards 
and inwards direction and historic usage data used for diagnostics:

F O R   M O U N T I N G   I N S T R U C T I O N S   A N D   G U I D A N C E   I N   U S A G E ,   P L E A S E   S E E   T H E   R E L E V A N T   U S E R   M A N U A L S

Copyright © LINAK 

2021.11 

. MA-M9-02-844

 . LINAK 

A/S reserves the right to mak

e technical alter

ations

READ ONL

Y

LINAK specific parameters

Index Field size

Description

Comment

Resolution/encoding

4096

U8

Current limit out

Set a default current limit

0.25 A/bit

4097

U8

Current limit in

4098

U16

Soft start time out

Set ramp-up speed settings

1 ms/bit

4099

U16

Soft start time in

4100

U16

Soft stop time out

Set ramp-down speed settings

(0 = instant stop or set a value ≥ 300 ms)

1 ms/bit

4101

U16

Soft stop time in

4103

U16

Virtual limit - outwards

Set a virtual limit to stop before the physical 

endstop

0.1 mm/bit

4104

U16

Virtual limit - inwards

4107

U32

Unique identification number

General information

U32 number

4111

U32

Software configuration number

4113

U8

Max. current seen

Monitor the max. current level (A)

0.25 A/bit

4115

U8

Max. temperature seen

Monitor the min. and max. 

temperature level (°C)

1 °C/bit (-40 °C offset)

4116

U8

Lowest temperature seen

4118

U32

Total runtime

Monitor the total runtime (s)

1 s/bit

4119

U16

Reason for last stop

(error codes)

0 = none, 1 = H-bridge fault, 2 = Temperature error, 4 = Undervoltage, 8 = Overcurrent, 

16 = Internal PSU failure, 32 = EOS fault, 64 = Hall fault, 256 = Overvoltage, 

512 = Position not changing, 1024 = Current measurement HW failure

4126

U8

Number of LINAK current overloads out

Monitor the number of times the actuator has 

stopped on the factory set current limit

1 time/bit

4127

U8

Number of LINAK current overloads in 

4128

U8

Number of customer overloads out

Monitor the number of times the actuator has 

stopped on the customer specific current limit

4129

U8

Number of customer overloads in

4131

U32

Number of end of stroke out

Monitor the number of endstop signals in each 

direction

4132

U32

Number of end of strokes in

4133

U32

Number of starts out

Monitor the number of starts in each 

direction

4134

U32

Number of starts in

4135

U32

Total piston distance

Monitor the distance travelled (m)

5 m/bit

4136

U32

Actuator production order number

General information

U32 number

Summary of Contents for BusLink LA25

Page 1: ...LINAK COM TECHLINE Actuator LA25 IO Link Quick start guide Version 1 1...

Page 2: ...lours from the actuator and the M12 port numbers are specified in the table below In a setup where the violet and white wires are not used we strongly recommend insulating these to avoid short circuit...

Page 3: ...supply 18 30 VDC On voltage 18 to 30 V M12 plug on device M12 Plug on device 3 2 1 4 5 2L 2M L C Q L pin numbering and connections Black M12 port 3 L IO Link supply 18 30 VDC GND Green M12 port 4 C Q...

Page 4: ...r LA25 The table below provides an overview of the input and output data Data name Byte Field size Details Set position Run command 0 1 16 bit 0x0000 0xFFEF 0 65519 0xFFFB 0XFFF0 65520 65531 0xFFFC 65...

Page 5: ...dentification number General information U32 number 4111 U32 Software configuration number 4113 U8 Max current seen Monitor the max current level A 0 25 A bit 4115 U8 Max temperature seen Monitor the...

Page 6: ...otor seperately read more here Plug in the M12 connector or wire up the actuator with flying leads to the master Make sure you receive data from the actuator Indicating that communication is OK Make s...

Page 7: ...on the product label max 2 5 amps on a standard LA25 Still experiencing problems with your actuator Please contact your local LINAK office for technical support Where can I find the latest IODD file...

Page 8: ...O U N T I N G I N S T R U C T I O N S A N D G U I D A N C E I N U S A G E P L E A S E S E E T H E R E L E V A N T U S E R M A N U A L S Copyright LINAK 2021 11 MA M9 02 844 LINAK A S reserves the rig...

Page 9: ...elopment in order to improve its products LINAK products are subject to frequent modifications and changes without prior notice Therefore LINAK cannot guarantee the correct and actual status of said i...

Reviews: